5
|
Preparation
Installer and user reference guide
45
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
Model
Z
max
(Ω)
Minimum S
sc
value
(kVA)
RYYQ24/RXYQ24
—
11597
RYYQ26/RXYQ26
—
12831
RYYQ28/RXYQ28
—
13585
RYYQ30/RXYQ30
—
14843
RYYQ32/RXYQ32
—
15094
RYYQ34/RXYQ34
—
16352
RYYQ36/RXYQ36
—
17359
RYYQ38/RXYQ38
—
19397
RYYQ40/RXYQ40
—
20378
RYYQ42/RXYQ42
—
20629
RYYQ44/RXYQ44
—
21132
RYYQ46/RXYQ46
—
21887
RYYQ48/RXYQ48
—
22641
RYYQ50/RXYQ50
—
23899
RYYQ52/RXYQ52
—
25157
RYYQ54/RXYQ54
—
26415
INFORMATION
Multi units are standard combinations.
5.4.3 Safety device requirements
The power supply must be protected with the required safety devices, i.e. a main
switch, a slow blow fuse on each phase and an earth leakage protector in
accordance with the applicable legislation.
For standard combinations
Selection and sizing of the wiring should be done in accordance with the applicable
legislation based on the information mentioned in the table below.
INFORMATION
Multi units are standard combinations.
Model
Minimum circuit
ampacity
Recommended
fuses
RYYQ8/RYMQ8/RXYQ8
16.1 A
20 A
RYYQ10/RYMQ10/RXYQ10
22.0 A
25 A
RYYQ12/RYMQ12/RXYQ12
24.0 A
32 A
RYYQ14/RYMQ14/RXYQ14
27.0 A
32 A
RYYQ16/RYMQ16/RXYQ16
31.0 A
40 A
RYYQ18/RYMQ18/RXYQ18
35.0 A
40 A