5
|
Preparation
Installer and user reference guide
35
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
There is never a connection of the equalising pipe with the indoor units.
Example:
(free multi combination)
RYMQ8+RYMQ18. Largest connection is Ø28.6 (RYMQ18); Ø22.2
(RYMQ12) and Ø19.1 (RYMQ8). In figure below only equalising pipe is shown.
Ø22.2 mm
Ø28.6 mm
Ø19.1 mm
INFORMATION
Reducers or T-joints are field supplied.
NOTICE
Refrigerant branch kits can only be used with R410A.
5.3.4 About the piping length
Make sure to perform the piping installation within the range of the maximum
allowable pipe length, allowable level difference and allowable length after
branching as indicated below. Three patterns will be discussed, including VRV DX
indoor units combined with Hydrobox units or RA DX indoor units.
Definitions
Term
Definition
Actual piping length
Pipe length between outdoor
(a)
and indoor units.
Equivalent piping length
(b)
Pipe length between outdoor
(a)
and indoor units.
Total piping length
Total piping length from the outdoor
(a)
to all indoor
units.
H1
Difference in height between outdoor and indoor
units.
H2
Difference in height between indoor and indoor
units.
H3
Difference in height between outdoor and outdoor
units.
H4
Difference in height between outdoor and BP unit.
H5
Difference in height between BP unit and BP unit.
H6
Difference in height between BP unit and RA DX
indoor unit.
(a) If the system capacity is a multi outdoor installation, re-read "the first outdoor
branch as seen from the indoor unit".
(b) Assume equivalent piping length of refnet joint=0.5 m and refnet header=1 m (for
calculation purposes of equivalent piping length, not for refrigerant charge
calculations).
5.3.5 Piping length: VRV DX only
For system only containing VRV DX indoor units: