Installation
Si39-303
40
General Information
Piping Diameter
for Grouped
Drain Pipes
!
Select piping diameter from the below table in accordance with the amount of condensation drained by
all units with a common drain pipe.
!
Consider 2 l/hr of drainage for every 1 HP. For example, drainage from 3 units running at 2 HP and 2
units running at 3 HP is calculated as follows.
2 (l/hr) × 2 (HP) × 3 (units) + { 2 (l/hr) × 3 (HP) × 2 (units) = 24 l/hr
1. Relationship between horizontal pipe diameter and allowable drainage (for extended ventilation system)
Notes:
!
Calculations have been made with water area inside the pipe as 10%.
!
Allowable flow rate figures below the decimal have been discarded.
!
Use VP30 or larger pipe after the convergence point.
2. Relationship between riser diameter and allowable drainage (for extended ventilation system)
Notes:
!
Allowed flow rate figures below the decimal have been discarded.
!
Use VP30 or larger pipe in risers.
!
Use the same drain pipe for the humidifier as the indoor unit.
3.2.9 Drain Piping for Each Model
Ceiling Mounted
Cassette Type
(FXCQ-M Double
flow)
1. Rig drain piping
!
The diameter of the drain pipe should be greater than or equal to the diameter of the connecting pipe
(vinyl tube, pipe size: 25 mm; outer dimension: 32 mm).
!
Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air pockets
from forming.
!
If the drain hose cannot be sufficiently set on a slope, execute the drain raising piping.
!
To keep the drain hose from sagging, space hanging wires every 1 to 1.5 m.
!
Use the attached drain hose and clamp metal.
Insert the drain hose into the drain socket, up to the white tape. Tighten the clamp until the screw head
is less than 4mm from the hose.
!
Wrap the attached sealing pad over the clamp and drain hose to insulate.
JIS nominal
Vinyl chloride pipe
diameter (mm)
Allowable flow rate (l/hr)
Remarks
Piping gradient 1:50
Piping gradient 1:100
VP20
20
39
27
(Reference value) Cannot
be used in grouped piping.
VP25
25
70
50
VP30
31
125
88
Can be used in grouped
piping.
VP40
40
247
175
VP50
51
473
334
JIS nominal
Vinyl chloride pipe
diameter (mm)
Allowable flow rate
(l/hr)
Remarks
VP20
20
220
(Reference value) Cannot
be used in grouped piping.
VP25
25
410
VP30
31
730
Can be used in grouped
piping.
VP40
40
1440
VP50
51
2760
VP65
67
5710
VP75
77
8280
Содержание VRV II Series
Страница 6: ...Si39 303 iv Table of Contents...
Страница 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Страница 124: ...Appendix Si39 303 118 General Information 3P114237A...
Страница 130: ...Appendix Si39 303 124 General Information BHFP22M135 Refer P 120 for Table 7 8 and 9 After connection piping...
Страница 140: ...Appendix Si39 303 134 General Information 7 10 Piping System Diagrams 7 10 1 Outdoor Unit RXYQ5MY1B...
Страница 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Страница 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Страница 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Страница 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Страница 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Страница 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Страница 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Страница 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Страница 158: ...Appendix Si39 303 152 General Information...
Страница 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Страница 226: ...Troubleshooting Si39 303 220 Operation Manual...