Si39-303
176
Installation Manual
Opening shutoff valve
1. Remove the cap and turn the valve counterclockwise with the hexagon wrench (JISB4648).
2. Turn it until the shaft stops.
Do not apply excessive force to the shutoff valve. Doing so may break the valve body, as the
valve is not a backseat type. Always use the special tool.
3. Make sure to tighten the cap securely.
Closing shutoff valve
1. Remove the cap and turn the valve clockwise with the hexagon wrench (JISB4648).
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
* For the tightening torque, refer to the table on the bellow.
Tightening torque
1.Service port
2.Cap
3.Hexagon hole
4.Shaft
5.Seal
Caution
!
Always use a charge hose for service port connection.
!
After tightening the cap, check that no refrigerant leaks are present.
!
When loosening a flare nut, always use two wrenches in combination. When connecting the
piping, always use a spanner and torque wrench in combination to tighten the flare nut.
!
When connecting a flare nut, coat the flare (inner and outer faces)
with etheral oil or ester oil and hand-tighten the nut 3 to 4 turns as
the initial tightening.
Flare shape and flare nut tightening torque
<Precautions when connecting pipes>
!
See the following table for flare part machining dimensions.
!
φ
12.7 or greater
When loosening a flare nut, always use two wrenches in combination. When connecting the
piping, always use a spanner and torque wrench in combination to tighten the flare nut.
!
φ
6.4 or
φ
9.7
Tighten with one torque wrench within the set torque.
(Do not use two wrenches because this might cause the refrigerant to leak.)
!
(Use ester oil or ether oil.)
!
See the following table for tightening torque.
(Applying too much torque may cause the flares to crack.)
Shutoff
valve size
Tightening torque N-m (Turn clockwise to close)
Shaft (valve body)
Cap (valve lid)
Service port
Flare nut
Gas line
piping
attached to
unit (1)
φ
6.4
5.4-6.6
Hexagonal
wrench
4 mm
13.5-16.5
11.5-13.9
14-17
_
φ
9.5
33-39
φ
12.7
8.1-9.9
18-22
50-60
φ
15.9
13.5-16.5
Hexagonal
wrench
6 mm
23-27
62-75
φ
22.2
27-33
Hexagonal
wrench
10 mm
36-44
_
22-28
φ
25.4
1
2
3
4
5
Torque wrench
Spanner
Piping union
Flare nut
Содержание VRV II Series
Страница 6: ...Si39 303 iv Table of Contents...
Страница 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Страница 124: ...Appendix Si39 303 118 General Information 3P114237A...
Страница 130: ...Appendix Si39 303 124 General Information BHFP22M135 Refer P 120 for Table 7 8 and 9 After connection piping...
Страница 140: ...Appendix Si39 303 134 General Information 7 10 Piping System Diagrams 7 10 1 Outdoor Unit RXYQ5MY1B...
Страница 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Страница 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Страница 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Страница 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Страница 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Страница 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Страница 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Страница 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Страница 158: ...Appendix Si39 303 152 General Information...
Страница 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Страница 226: ...Troubleshooting Si39 303 220 Operation Manual...