Appendix
Si39-303
106
General Information
7. Appendix
7.1
Operating Noise of Indoor Units
7.1.1 Difference between Catalogue Data and Actual Noise
Operating noise differs depending on the place of measurement (room) because of the various degrees
with which the room reverberates the sound. To determine the amount of reverberation under uniform
conditions, the unit has been measured in a dead room with results having been compiled in the below
table. The actual sound produced in unit operation can be determined from Table 1.
Sound pressure rise due to room reverberation (Higher than catalogue data)
Table 1
Classifications of indoor unit environments (reference data)
Table 2
Notes:
1. Excluding bedrooms
2. Reference values of faint noises in the place of usage
A
B
C
Room Interior
Detection
Floor
Mortar
Linoleum tile
Carpet
Walls
Mortar
Plaster
Fibe
Saroncross finish
Ceiling
Mortar
mineral wool tile
Fibe
Saroncross finish
Average Absorbed Sound (Room with
Approx. 50 m² Floor Area)
0.05
0.12
0.25
Typical office
Estimated value to be added to
catalogue value
11~12
8~8.5
5~6
Classification
Environment
Example
Faint Noises
(NOTE 2)
Recommended
Operating Noise on Site
1
Non-active places requiring silence
Reception rooms, libraries, sitting rooms,
hospitals (examining rooms) (NOTE 1)
~35
~40
2
Sedate business activities that do not
disturb people even over time
Quiet offices, classrooms, small
conference rooms, lobbies
~40
~45
3
Somewhat quiet settings that permit
soft-spoken conversation, typical
activities
Small offices, large conferences rooms,
quiet stores, restaurants
~45
~50
4
Somewhat loud settings that permit
regular conversation, brisk activity
Large offices, typical stores, cafeterias
~50
~55
5
Loud places that permit conversation
in a loud voice, highly active place
with many people
Loud large-side offices, large cafeterias,
loud stores
~55
~60
6
Rather loud settings
Factories, gymnasiums, recreational
places like pachinko parlors
~60
~65
Содержание VRV II Series
Страница 6: ...Si39 303 iv Table of Contents...
Страница 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Страница 124: ...Appendix Si39 303 118 General Information 3P114237A...
Страница 130: ...Appendix Si39 303 124 General Information BHFP22M135 Refer P 120 for Table 7 8 and 9 After connection piping...
Страница 140: ...Appendix Si39 303 134 General Information 7 10 Piping System Diagrams 7 10 1 Outdoor Unit RXYQ5MY1B...
Страница 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Страница 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Страница 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Страница 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Страница 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Страница 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Страница 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Страница 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Страница 158: ...Appendix Si39 303 152 General Information...
Страница 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Страница 226: ...Troubleshooting Si39 303 220 Operation Manual...