Installation
Si39-303
30
General Information
Checking for
Leaks
[Check 1] (Where pressure falls while carrying out Steps 1 to 3 described on previous page)
!
Check by ear......Listen for the sound of a major leak.
!
Check by hand......Check for leak by feeling around jointed sections with hand.
!
Soap and water check (
∗
Snoop)......Bubbles will reveal the presence of a leak.
[Check 2] (When searching for a minor leak or when there has been a fall in pressure while the system has
been fully pressurized but the source of the leak cannot be traced.)
1. Release the nitrogen until the pressure reaches 0.3MPa.
2. Increase pressure to 1.5MPa using gaseous flon gas (R410A). (Nitrogen and flon gas mixed)
3. Search for the source of the leak using a leak detector.
4. If the source of the leak still cannot be traced then repressurize with nitrogen up to 3.80MPa and check
again. (The pressure must not be increased to more than 3.80MPa.)
Setup of Air-light Test
As for the air-tight test, the setup of devices shown in the following figure is recommended with
considerations given to “vacuum drying and refrigerant additional charging”, which are operation
steps following the air-tightness test.
In order to conduct the air-tight test, with stop valves of 8.Gas side, 10.liquid side and 15.Oil
equalization piping and those of the refrigerant and vacuum pump all closed, then open the
nitrogen gas stop valve, 7.Valve A, and 16.Valve B while adjusting the nitrogen gas pressure
regulating valve, thus increasing the pressure.
One outdoor unit installed: In case of RXYQ5-16MY1B
1.Pressure reducing valve
2.Nitrogen
3.Refrigerant cylinder
4.Siphon system
5.Measuring instrument
6.Vacuum pump
7.Valve A
8.Gas side
9.Outdoor unit
10.Liquid side
11.Indoor unit
12.Shutoff valve service port
13.Charge hose
14.To indoor unit
15.Oil-equalizing line
16.Valve B
17.Dotted lines represent onsite piping
!
Important points
1. Where the lengths of piping involved are particularly long then the air tight test should be carried out
block by block.
Example:
1. Indoor side
2. Indoor side + vertical pipes
3. Indoor side + vertical pipes + outdoor side
1
1
2
2
3
3
4
4
5
5
6
6
7
7
13
12
14
8
9
9
8
9
10
10
15
11
12
17
16
17
13
When multiple outdoor units installed:
In case of RXYQ18-48MY1B
Содержание VRV II Series
Страница 6: ...Si39 303 iv Table of Contents...
Страница 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Страница 124: ...Appendix Si39 303 118 General Information 3P114237A...
Страница 130: ...Appendix Si39 303 124 General Information BHFP22M135 Refer P 120 for Table 7 8 and 9 After connection piping...
Страница 140: ...Appendix Si39 303 134 General Information 7 10 Piping System Diagrams 7 10 1 Outdoor Unit RXYQ5MY1B...
Страница 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Страница 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Страница 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Страница 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Страница 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Страница 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Страница 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Страница 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Страница 158: ...Appendix Si39 303 152 General Information...
Страница 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Страница 226: ...Troubleshooting Si39 303 220 Operation Manual...