SiUS12-928_B
Control Specification
Function and Control
58
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows. (The
function is not used when defrosting.)
3.4
Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Detail
A
(Hz)
55
B
(Hz)
65
C
(Hz)
80
D
(seconds)
120
E
(seconds)
200
F
(seconds)
470
A
D
E
F
B
C
(R13528)
(Hz)
Frequency
(sec.)
Time
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Reset zone
The upper limit of frequency is canceled.
24
8
°F (120°C)
231.
8
°F (111°C)
22
8
.2°F (109°C)
224.6°F (107°C)
224.6°F (107°C)
A
B
C
D
E
Reset zone
Stop zone
Dropping
zone
Keep
zone
(R14266)
A
C
D
E
B
Discharge pipe
temperat
u
re
The temperat
u
res
D
and
E
are the same.
Содержание SUPER MULTI NX CDXS18LVJU
Страница 1: ...Service Manual G Series J Series SiUS12 928_B Applied Models Inverter Multi Heat Pump ...
Страница 9: ...SiUS12 928_B 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 15: ...SiUS12 928_B 7 Specifications Part 2 Specifications 1 Indoor Unit 8 2 Outdoor Unit 13 ...
Страница 118: ...SiUS12 928_B CTXS L FTXS L Series Operation Manual 110 3 12 Quick Reference Quick Reference C 3P297290 1 C 3P297290 2 ...
Страница 140: ...SiUS12 928_B CDXS L FDXS L Series Operation Manual 132 5 10 Quick Reference Quick Reference C 3P297290 3 ...