Indoor Unit
SiUS12-928_B
27
Printed Circuit Board Connector Wiring Diagram
1.5
FDXS09/12LVJU, CDXS15/18LVJU
Connectors and
Other Parts
A1P: Control PCB
A2P: Display PCB
Caution
Replace the PCB if you accidentally cut the jumpers other than JA, JB, and JC.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
1) S1
Connector for AC fan motor
2) S7
Connector for AC fan motor (Hall IC)
3) S21
Connector for centralized control (HA)
4) S26
Connector for display PCB
5) S32
Connector for indoor heat exchanger thermistor
6) H1, H2, H3
Connector for terminal board
7) FG (GND)
Connector for terminal board (ground)
8) JA
Address setting jumper
Refer to page 265 for detail.
9) JB
Fan speed setting when compressor stops for thermostat OFF
JC
Power failure recovery function (auto-restart)
Refer to page 266 for detail.
10) LED A
LED for service monitor (green)
11) FU1 (F1U)
Fuse (3.15 A, 250 V)
12) V1 (V1TR)
Varistor
1) S1
Connector for control PCB
2) SW1 (S1W)
Forced operation [ON/OFF] button
3) LED2 (H2P)
LED for timer (yellow)
4) LED3 (H3P)
LED for operation (green)
5) RTH1 (R1T)
Room temperature thermistor
Содержание SUPER MULTI NX CDXS18LVJU
Страница 1: ...Service Manual G Series J Series SiUS12 928_B Applied Models Inverter Multi Heat Pump ...
Страница 9: ...SiUS12 928_B 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 15: ...SiUS12 928_B 7 Specifications Part 2 Specifications 1 Indoor Unit 8 2 Outdoor Unit 13 ...
Страница 118: ...SiUS12 928_B CTXS L FTXS L Series Operation Manual 110 3 12 Quick Reference Quick Reference C 3P297290 1 C 3P297290 2 ...
Страница 140: ...SiUS12 928_B CDXS L FDXS L Series Operation Manual 132 5 10 Quick Reference Quick Reference C 3P297290 3 ...