SiUS12-928_B
Troubleshooting for Outdoor Unit
Service Diagnosis
178
Troubleshooting
24/32 class
Check No.15
Refer to P.196
Check No.18
Refer to P.198
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Check the power supply voltage.
Check the connection.
Turn off the power.
Correct the power supply.
Voltage as rated?
(R15892)
NO
NO
YES
NO
YES
YES
Check No.15
Check with the inverter checker (
∗
).
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power.
Check the electrolytic capacitor
voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB.
Replace the compressor.
Correct the power supply or
replace the outdoor unit
PCB.
Reconnect the electrical
components or compressor
harnesses as specified.
∗
Inverter checker
Part No.: 1225477
320 ± 50 VDC?
Any LED OFF?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
Содержание SUPER MULTI NX CDXS18LVJU
Страница 1: ...Service Manual G Series J Series SiUS12 928_B Applied Models Inverter Multi Heat Pump ...
Страница 9: ...SiUS12 928_B 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 15: ...SiUS12 928_B 7 Specifications Part 2 Specifications 1 Indoor Unit 8 2 Outdoor Unit 13 ...
Страница 118: ...SiUS12 928_B CTXS L FTXS L Series Operation Manual 110 3 12 Quick Reference Quick Reference C 3P297290 1 C 3P297290 2 ...
Страница 140: ...SiUS12 928_B CDXS L FDXS L Series Operation Manual 132 5 10 Quick Reference Quick Reference C 3P297290 3 ...