Main Functions
SiE12-411
74
Function and Control
1.4
Programme Dry Function
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and air flow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
In Case of
Inverter Units
The microcomputer automatically sets the temperature and fan settings. The difference
between the room temperature at startup and the temperature set by the microcomputer is
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Room temperature at
startup
Temperature (ON point)
at which operation starts
Frequency switching
point
Temperature difference
for operation stop
24ºC
Room temperature at
startup
0.5ºC
1.5ºC
18ºC
18ºC
1.0ºC
17ºC
—
0.5°C
LHz
LHz
LHz
*
55Hz
*
55Hz
LHz indic
a
te
s
low fre
qu
ency. Item m
a
rked with v
a
rie
s
depending on model
s
.
ON point
OFF point
5 min
5 min
S
top
S
top
S
top
S
top
S
top
S
top
Indoor
u
nit f
a
n
Extr
a
-low
a
ir flow
Extr
a
-low
a
ir flow
Low
a
ir flow
Low
a
ir flow
(R1
3
59)
Fre
qu
ency
s
witching
point
Compre
ss
or
control
Содержание Super Multi NX C-Series
Страница 1: ...SiE12 411 Service Manual C Series Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump...
Страница 6: ...SiE12 411 Table of Contents v Index i Drawings Flow Charts v...
Страница 7: ...SiE12 411 vi Table of Contents...
Страница 67: ...Specifications SiE12 411 56 Specifications...
Страница 129: ...Instruction SiE12 411 118 System Configuration CDK X D 25 35 50 60 C Indoor Unit 3 6 8 9 10 7 1 4 5 2...
Страница 171: ...Instruction SiE12 411 160 System Configuration...
Страница 225: ...Check SiE12 411 214 Service Diagnosis...
Страница 266: ...SiE12 411 Others 255 Part 8 Others 1 Others 256 1 1 Test Run from the Remote Controller 256 1 2 Jumper Settings 257...
Страница 295: ...SiE12 411 iv Index...