Troubleshooting
SiE12-411
196
Service Diagnosis
5.21 Radiation Fin Temperature Rise
Remote
Controller
Display
L4
Outdoor Unit LED
Display
A
5
1
1
2
1
3
1
4
4
Method of
Malfunction
Detection
A radiation fin temperature rise is detected by checking the radiation fin temperature being
detected by the fin thermistor with the compressor on.
Malfunction
Decision
Conditions
If the radiation fin temperature with the compressor on is above 90°C for 5.2~7.5 kW-or-smaller
class systems or above 85°C for 8.0 · 9.0 kW class systems,
"
If a radiation fin temperature rise takes place 4 times successively, the system will be shut
down.
"
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
"
Fin temperature rise due to defective outdoor unit fan
"
Fin temperature rise due to short-circuit
"
Fin thermistor defective
"
Connector in poor contact
"
Outdoor unit PCB defective
Содержание Super Multi NX C-Series
Страница 1: ...SiE12 411 Service Manual C Series Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump...
Страница 6: ...SiE12 411 Table of Contents v Index i Drawings Flow Charts v...
Страница 7: ...SiE12 411 vi Table of Contents...
Страница 67: ...Specifications SiE12 411 56 Specifications...
Страница 129: ...Instruction SiE12 411 118 System Configuration CDK X D 25 35 50 60 C Indoor Unit 3 6 8 9 10 7 1 4 5 2...
Страница 171: ...Instruction SiE12 411 160 System Configuration...
Страница 225: ...Check SiE12 411 214 Service Diagnosis...
Страница 266: ...SiE12 411 Others 255 Part 8 Others 1 Others 256 1 1 Test Run from the Remote Controller 256 1 2 Jumper Settings 257...
Страница 295: ...SiE12 411 iv Index...