Outdoor Unit (80 / 90 Class)
SiE12-411
222
Removal Procedure
2. Remove each wire harness
1
Disconnect 4
connectors of the
electronic expansion
valve lead wires.
"
When reconnecting, make
sure to match the wire to the
correct connector.
2
Remove the four way
valve connector S80.
3
Remove the connector
S93 for liquid pipe
thermistor.
Step
Procedure
Points
S
20
white
S
21
red
S
22
b
l
u
e
S
2
3
yellow
Connector
Electronic
expansion
valve No.
Harness
length
S20 (White)
EVA
630
S21 (Red)
EVB
730
S22 (Blue)
EVC
825
S23 (Yellow)
EVD
940
S8
0
S