Outdoor Unit (80 / 90 Class)
SiE12-411
230
Removal Procedure
1.5
Removal of Fan Motor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
"
Remove the outer panels.
1
Remove the fan motor
lead wire connector
S70.
2
Remove the propeller
fans.
"
For reassembling, align
mark of propeller fan with
D-cut section of motor shaft.
"
Mount the fan motor so as to
position
!
mark on the top.
3
Remove 2 screws of
the fan motor mount.
S
70
W
as
her-fitted n
u
t M
8