- 32 -
Chapter 4 Recording of operation data
The window of [Periodical record setting]
Procedures
1) Set the [1.Recording interval], the [2. Recording end method], and the [3. Recording system
selection].
Setting item
Description
1. Recording
interval
1) Select the time intervals recording in the hard disk of the personal
computer.(5, 10, 20, 30, 60, 120, 180, 300, 600 seconds)
2) Since less time intervals need more recording data area for the hard
disk, the initially set value of 20 seconds is recommended.
3) When recording for a long time (more than 2-3 days), it is
recommended that the recording interval should be 120 to 300
seconds.
* The recording interval is an interval recorded in the hard disk of the
personal computer. The operation data taken in from each air
conditioner may be recorded at intervals of several minutes in case of
indoor units.
2. Recording
end method
Set a recording stop method as follows.
Manual :
In the window of the [Network Map Display], continue to
record until pressing the [Periodical record stop(F7)]
button.
Automatic : Recording of operation data ends automatically after
arriving at a pre-set recording time. Input a recording time
with a minute unit.
3. Recording
system
selection
1) In the DIII-NET connection, it is possible to set [Recording] or[No
recording] for every system(each outdoor unit). Multiple selection is
possible.
2) By placing the cursor in the [System No.] to press the [F12] key,
[Recording] or [No recording] is shifted. The left side of system
recording is marked .
(Notes)
Since the [Total of expected record file size(KB/hour(s))] and the [Free hard disk
area (MB)] are displayed, confirm if the free area is enough in recording the data.
Be careful to note that if the free hard disk area of the personal computer is more
than 2 GB, values may not be displayed correctly.