- 23 -
Chapter 4 Recording of operation data
4.1.2 Displaying of network map
(Notes)
If time setting of the personal computer is made after the window of the [Network Map
Display], the order of data to be recorded is changed, resulting in not recording data
correctly. Do not make time setting of the personal computer after the window of the
[Network Map Display].
* When the Checker TYPE 3 is connected to the DIII-NET for the first time, air
conditioners on the DIII-NET will be set to restart standby for several minutes,
displaying the following message.
* If the restart-standby is allowed, press the [Yes(F1)].
(Notes)
1. When pressing the [Yes(F1)], air conditioners on the DIII-NET are set to restart
standby, making the thermostat switched off for several minutes.
2. If using the previous network data by customer management, no such message
in the window will be displayed again from the second time.
Then, air conditioners on the DIII-NET are automatically searched for several
minutes.
(Note)
When the wiring-change button on the PCB is not pressed after adding or
removing an outdoor unit, an indoor unit, and BS unit and changing PCB, the
network map may not be displayed. In such a case, press the wiring-change
button.
* If the restart-standby is not allowed, press the [No(ESC)] to return to the
previous stage and monitor every outdoor unit by PCB connection.