7
Parameter settings
Operating Instructions
42
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
7.6.6
Menu: Additional programs
[→ Main menu → Configuration → Addition]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Relay test
Manual control of individual relays for test purposes. After confirmation of
this parameter with the rotary button, the list of relays 1 – 9 is displayed
with a checkbox on the display. For selection and confirmation of a relay
with the rotary button, a tick is placed in the checkbox and the respective
relay is activated. Multiple selection is possible.
-
-
N
E
Output J1
Output J1 (internal heating circulation pump), output pump
Output J14
Output J14 (circulation pump), mixer "Open"
Output J2 con-
tact A
Contact A on output J2 (switching valve 3UVB1), mixer "Closed"
Output J2 con-
tact B
Contact B on output J2 (switching valve 3UVB1)
Output J12 3UV
DHW open
Output J12, switching valve 3UV DHW "Closed"
Output J12 3UV
DHW closed
Output J12, switching valve 3UV DHW "Open"
Connection J3
N/O contact B
Connection J3 (potential-free relay: normally open B-B1) – AUX
Connec. J3
changeover
contact A
Connection J3 (potential-free relay: Changer A-A1/A-A2) – AUX
Output J10
Output J10 (A1P power supply)
Output J17 relay
K2
Output J17 (pin 3) – relay K2 (RTX-EHS) output XBUH1 T2
Output J17 relay
K1
Output J17 (pin 2) – relay K1 (RTX-EHS) output XBUH1 T3
Output J17 relay
K3
Output J17 (pin 4) – relay K3 (RTX-EHS) output XBUH1 T1
Ventilation
function
Activation of automatic ventilation of the Daikin Altherma ETS(X/H) and the
connected HC.
-
N
E
Off
Deactivated
On
Start of the ventilation function
Screed
Function for screed drying
-
N
E
Off
Deactivated
On
The feed target temperature is regulated according to the set [Screed pro-
gram]. The day on which the screed function is activated is not included in
the running time of the screed program. The first day starts when the day
changes at 00:00 am. On the day of activation, heating is carried out for
the remaining time with the feed target temperature of the program of the
first day (see
Screed pro-
gram
10 – 70 °C per
heating day
Setting of the sequence program of the screed heating. An individual feed
target temperature can be set for each day for a maximum duration of 28
days. The end of the screed program is defined by the 1st day with the tar-
get value setting "Off" (see
).
See
1 °C
N
E
Tab. 7-18
Parameter in the "Additional programs" menu
Содержание RoCon+ HP Series
Страница 57: ...Operating Instructions 57 Daikin RoCon HP Daikin controller RoCon HP1 008 1447899_00 09 2019 EN ...
Страница 114: ...12 Notizen Betriebsanleitung 114 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE 12 Notizen ...
Страница 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Страница 174: ...12 Notes Manuel d utilisation 174 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR 12 Notes ...
Страница 176: ...Manuel d utilisation 176 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR ...
Страница 178: ...Inhoud Gebruiksaanwijzing 178 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL Trefwoordenlijst 235 ...
Страница 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Страница 295: ...12 Appunti Istruzioni per l uso 295 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT 12 Appunti ...
Страница 297: ...Istruzioni per l uso 297 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT ...
Страница 349: ...12 Notitser Driftsvejledning 349 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA 12 Notitser ...
Страница 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Страница 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Страница 458: ...12 Notater Brukerveiledning 458 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO 12 Notater ...
Страница 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Страница 462: ...Sisällysluettelo Käyttöohje 462 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI Hakemisto 515 ...
Страница 514: ...12 Muistiinpanoja Käyttöohje 514 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI 12 Muistiinpanoja ...
Страница 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...