Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Feed temper-
ature, over-
shoot (*)
0 – 4
This function defines how far the water temperature may exceed the feed
target temperature before the compressor is stopped. The compressor re-
sumes operation when the feed temperature falls below the target feed
temperature. This function ONLY applies to heating mode.
3
1
N
E
Feed temper-
ature, heating
mode
20 – 90 °C
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the target feed temperature for the heating circuit during the
heating time in operating mode: "Automatic 1", "Automatic 2", "Heating".
40 °C
1 °C
E
E
Feed temper-
ature, reducing
mode
10 – 90 °C
Only if [Weather-compensated] parameter = Weather-compensated:
Setting the target feed temperature for the heating circuit during the set-
back time for the operating mode: "Automatic 1", "Automatic 2", "Heating".
10 °C
1 °C
E
E
Max. feed tem-
perature
20 – 90 °C
The setting limits the feed temperature (measured at t
V2
) with active heat-
ing support function.
The determined target feed temperature of the HC is limited to the max-
imum value set here.
If an optionally connected mixed HC requests a higher temperature of the
heat generator, this is taken into account. This means the internal circula-
tion pump of the heat generator always runs if the generator is switched
on. If the direct HC supplies the floor heating, a mechanical temperature
limiter must be installed to prevent any overheating of the screed.
80 °C
1 °C
N
E
Min. feed tem-
perature
10 – 90 °C
The determined flow target temperature of the heating circuit is limited to
the minimum value set here.
10 °C
1 °C
N
E
Room influ-
ence
Only with the room control connected and assigned to the HC:
The setting of what influence the deviation of the room temperature meas-
ured by EHS157034 from the current target value (see
the feed temperature.
1 K
E
E
Off
Purely weather-compensated feed temperature control
0 K
Purely weather-compensated feed temperature control, but internal circula-
tion pump continues running until the next heating cycle after a heat re-
quirement during the setback cycle.
1 – 20 K
Causes a correction of the target feed temperature (parallel shift of the
heating curve) by the set factor. If the measured temperature lies 2 K be-
low the target value, the target feed temperature is increased by 2x the set
value.
Room sensor
adaptation
-5 – +5 K
Only with room control connected and assigned to the HC.
Individual adjustment of the room temperature relevant to the controller.
If a systematic deviation of the room temperature measured by the
EHS157034 to the actual temperature in the occupied area of this room is
determined, the measured value can be corrected by the set value.
0.0 K
1 K
E
E
Heating curve
adaptation
The function can only be carried out with a room controller connected and
assigned to the HC:
-
N
E
Off
Deactivated
On
Activated = start of a one-time automatic heating curve adaptation.
Prerequisites:
▪ Outside temperature < 8 °C
▪ Setting of the operating mode: "Automatic 1" or "Automatic 2"
▪ Duration of the setback period is at least 6 hours
Function: At the start of the setback time, the current room temperature is
set as the target value for the following 4 hours. The heating curve that is
required to maintain this room temperature is determined from the target
feed temperature by the controller.
If the automatic heating curve adaptation is interrupted, the function
pauses until the adaptation is successfully carried out or ended the next
day (setting the parameter to "Off" or changing the current operating
mode).
Domestic hot water preparation and heating optimisation is locked during
the automatic heating curve adaptation.
Interlink tem-
perature in-
crease
1 – 50 K
Only if [Interlink function] parameter = On:
Feed target temperature is increased by the set value when the cooling RT
switching contact is closed. Request, e.g. by HP convector.
5 K
1 K
N
E
Содержание RoCon+ HP Series
Страница 57: ...Operating Instructions 57 Daikin RoCon HP Daikin controller RoCon HP1 008 1447899_00 09 2019 EN ...
Страница 114: ...12 Notizen Betriebsanleitung 114 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE 12 Notizen ...
Страница 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Страница 174: ...12 Notes Manuel d utilisation 174 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR 12 Notes ...
Страница 176: ...Manuel d utilisation 176 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR ...
Страница 178: ...Inhoud Gebruiksaanwijzing 178 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL Trefwoordenlijst 235 ...
Страница 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Страница 295: ...12 Appunti Istruzioni per l uso 295 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT 12 Appunti ...
Страница 297: ...Istruzioni per l uso 297 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT ...
Страница 349: ...12 Notitser Driftsvejledning 349 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA 12 Notitser ...
Страница 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Страница 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Страница 458: ...12 Notater Brukerveiledning 458 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO 12 Notater ...
Страница 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Страница 462: ...Sisällysluettelo Käyttöohje 462 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI Hakemisto 515 ...
Страница 514: ...12 Muistiinpanoja Käyttöohje 514 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI 12 Muistiinpanoja ...
Страница 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...