![Daikin RoCon+ HP Series Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/daikin/rocon-hp-series/rocon-hp-series_operating-instructions-manual_501854018.webp)
4
Function
Operating Instructions
18
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Heating curve
WARNING: FLAMMABLE MATERIAL
In the event of malfunction, the floor heating system, the
screed or the floor structure could be damaged due to
overheating.
▪ Prior to initial commissioning, set the maximum temper-
ature limit in the RoCon+ HP controller ([Max. feed
temperature] parameter) to the maximum permitted
system temperature prior to starting the emission
measurement.
▪ Connect an overheating protection switch (in the build-
ing) at the "Ext" plug connection for external operating
mode switch-over so that the Daikin Altherma ETS(X/
H) is switched to the "Standby" or "Summer" operating
mode. If the [Room thermostat] parameter = Yesor the
[Interlink function] parameter = On, the overheating
protection switch must be connected so that the room
thermostat's switching contact is interrupted.
▪ If the floor heating is also used for room cooling, the
connection notes in the above point also apply to the
connection of a moisture protection switch in the build-
ing.
The heating curve is used to adapt the feed temperature to the char-
acteristics of the building independent of the respective outside tem-
perature (weather-compensated feed temperature control, see
). Generally speaking, the slope of the heating curve de-
scribes the ratio of the feed temperature change to the external tem-
perature change.
The heating curve is valid within the limits of the minimum and max-
imum temperatures set for the respective HC. The room temperature
measured in the occupied area may differ from the required room
temperature; these deviations can be kept to a minimum by installing
a room thermostat or a room control.
The
controller
is set at the
factory
in such a way that the
heating
curve
does
not independently adjust itself
during operation.
The
automatic heating curve adjustment
can be activated ([Heat-
ing curve adaptation] parameter)
if
the
outside temperature sensor
and the
room controller
(EHS157034) are
connected
(see
).
Start conditions for automatic heating curve adjustment:
▪ Outside temperature < 8 °C
▪ Operating mode is [Automatic 1] or [Automatic 2]
▪ Duration of the setback period is at least 6 h
If
no automatic heating curve adjustment
is activated, the heating
curve can be
manually
adjusted by
adjusting
the [Heating curve]
parameter
).
INFORMATION: MANUALLY ADJUSTING THE HEAT-
ING CURVE
Do not make any corrections to the set values for 1 – 2
days, and then only make them in small increments.
▪ Deactivate the external heat sources (e.g. stoves, dir-
ect sunlight, open windows).
▪ Fully open any radiator thermostat valves or actuators.
▪ Activate "Heating" operating mode. Approximate setting
values:
Heating element: 1.4 to 1.6.
Floor heating: 0.5 to 0.9.
Fig. 4-2
Heating curves
T
A
Outside temperature
T
R
Room target temperature
T
V
T-HS
Comfort heating
If the heat pump cannot cover the heating demand when outside
temperatures are very low, heat is extracted from the storage tank
and used for room heating. In rare cases (in systems with high re-
quired feed temperatures and low required hot water temperatures),
the required feed temperature can be higher than the storage tank
target temperature. In order to avoid short-term loss of comfort in
heating mode for these systems, the [Comfort heating] parameter
can be set to "On". At corresponding outside temperatures, the stor-
age tank temperature is raised above the storage tank temperature
set for the hot water requirement.
INFORMATION
If [Comfort heating] is set to "On", the power consumption
of the heat pump may increase. In the default setting,
[Comfort heating] is set to "Off".
Detailed explanations and possible setting values of this function can
be found in
.
4.5.5
Cooling
[→ Main menu → Configuration → Cooling]
This menu is used to make settings for cooling mode.
CAUTION: DANGER OF CONDENSATION
In the event of malfunction or incorrect parameter settings,
the floor heating, the screed or the floor structure could be
damaged due to condensation.
▪ Prior to initial commissioning and activation of cooling
mode, set the minimum temperature limit to the min-
imum permissible system temperature in the RoCon
controller (parameter [Feed temperature lower limit]).
Prerequisites for cooling mode:
▪ Outside temperature > set value of room target temperature
▪ Outside temperature > set value of the [Start cooling outside
temp.] parameter
▪ [Cooling] operating mode activated.
▪ via menu "Operating mode" or
▪ via room thermostat function (cooling switching contact closed)
Содержание RoCon+ HP Series
Страница 57: ...Operating Instructions 57 Daikin RoCon HP Daikin controller RoCon HP1 008 1447899_00 09 2019 EN ...
Страница 114: ...12 Notizen Betriebsanleitung 114 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE 12 Notizen ...
Страница 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Страница 174: ...12 Notes Manuel d utilisation 174 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR 12 Notes ...
Страница 176: ...Manuel d utilisation 176 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR ...
Страница 178: ...Inhoud Gebruiksaanwijzing 178 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL Trefwoordenlijst 235 ...
Страница 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Страница 295: ...12 Appunti Istruzioni per l uso 295 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT 12 Appunti ...
Страница 297: ...Istruzioni per l uso 297 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT ...
Страница 349: ...12 Notitser Driftsvejledning 349 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA 12 Notitser ...
Страница 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Страница 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Страница 458: ...12 Notater Brukerveiledning 458 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO 12 Notater ...
Страница 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Страница 462: ...Sisällysluettelo Käyttöohje 462 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI Hakemisto 515 ...
Страница 514: ...12 Muistiinpanoja Käyttöohje 514 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI 12 Muistiinpanoja ...
Страница 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...