![Daikin RoCon+ HP Series Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/daikin/rocon-hp-series/rocon-hp-series_operating-instructions-manual_501854033.webp)
7
Parameter settings
Operating Instructions
33
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Indoor unit
No selection
Heat pump interior unit type.
Adaptation of the set value important, as the device types have different
defrosting logics.
-
-
N
E
ETS(H/X)
(B)16P30D
ETS(H/X)
(B)16P50D
Heating sys-
tem (*)
Floor heating
Heat exchanger type in the heating system.
If "Radiator" is selected and high feed temperatures are desired, it may
make sense to increase the [Max. feed temperature] parameter to 65 °C
([→ Main menu → Configuration → Heating]).
-
N
E
Convector
Radiator
Pump dT heat-
ing (*)
3 – 10
Required temperature difference between return and feed temperature. If a
minimum temperature difference is required for good heat distribution sys-
tem operation in heating mode.
5
1
N
E
Pump dT cool-
ing (*)
3 – 10
Required temperature difference between return and feed temperature. If a
minimum temperature difference is required for good heat distribution sys-
tem operation in cooling mode.
5
1
N
E
Glycol (*)
No glycol added Adding glycol to the water circuit is recommended to guarantee frost pro-
tection in the event of a power failure. If glycol has been added to the sys-
tem, the RoCon+ controller setting must be adapted accordingly.
-
N
E
Glycol added
HP Power lim-
itation
20 – 50 A
The permanent power limitation is useful to ensure maximum power con-
sumption of the system. In some countries, legislation limits the maximum
power consumption for room heating and domestic hot water.
50 A
N
E
Pump limit
This parameter defines the maximum pump speed. Under normal condi-
tions, the default setting should NOT be changed. The limitation of the
pump speed is skipped if the flow rate is in the range of the minimum flow
rate. The water flow resulting at limited pump speed can be taken from the
pump characteristic curve (see Installation and maintenance instructions
Daikin Altherma ETS(X/H))
6
1
N
E
0
No limit
1 – 4
Limitation of pump speed independent of the operating status. This setting
cannot guarantee heating comfort. The maximum pump speed depends on
the setting as follows: 1: 90%, 2: 75%, 3: 65%, 4: 55%
5 – 8
Limitation of the pump speed if there is no heating or cooling requirement.
The maximum pump speed depends on the setting as follows: 5: 90%,
6: 75%, 7: 65%, 8: 55%
Tab. 7-9
Parameter in the "System" menu
7.5.3
Menu: External heat source
[→ Main menu → Settings → Ext. source]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Config. ext.
heat source
Setting of whether there is an additional external heat generator for do-
mestic hot water preparation (DHW) and/or heating support (HZU).
-
N
E
No external heat
generator
The heat pump is the only heat source
Backup heater
BUH
Optional heating rod (3N~) installed in the storage tank
DHW + heating
support
An alternative heat generator (e.g. backup heater 1N~) provides domestic
hot water preparation and backup heating
Two external
heat generators
Two external heat generators: Alternative WEZ 1 (e.g. backup heater 1N~)
takes over domestic hot water preparation and alternative WEZ 2 takes
over heating support
External power
hot water
1 – 40 kW
Heat output of the electric heater booster for domestic hot water prepara-
tion
3 kW
1 kW
N
E
External power
stage 1 (*)
1 – 40 kW
Heat output of the electric heater booster for heating support stage 1
See operating instructions for heating element EKBUxx.
3 kW
1 kW
N
E
External power
stage 2 (*)
1 – 40 kW
Heat output of the electric heater booster for heating support stage 2
See operating instructions for heating element EKBUxx.
3 kW
1 kW
N
E
Содержание RoCon+ HP Series
Страница 57: ...Operating Instructions 57 Daikin RoCon HP Daikin controller RoCon HP1 008 1447899_00 09 2019 EN ...
Страница 114: ...12 Notizen Betriebsanleitung 114 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE 12 Notizen ...
Страница 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Страница 174: ...12 Notes Manuel d utilisation 174 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR 12 Notes ...
Страница 176: ...Manuel d utilisation 176 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR ...
Страница 178: ...Inhoud Gebruiksaanwijzing 178 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL Trefwoordenlijst 235 ...
Страница 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Страница 295: ...12 Appunti Istruzioni per l uso 295 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT 12 Appunti ...
Страница 297: ...Istruzioni per l uso 297 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT ...
Страница 349: ...12 Notitser Driftsvejledning 349 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA 12 Notitser ...
Страница 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Страница 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Страница 458: ...12 Notater Brukerveiledning 458 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO 12 Notater ...
Страница 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Страница 462: ...Sisällysluettelo Käyttöohje 462 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI Hakemisto 515 ...
Страница 514: ...12 Muistiinpanoja Käyttöohje 514 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI 12 Muistiinpanoja ...
Страница 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...