Parameter settings
Operating Instructions
37
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Heating sup-
port power
3 – 40 kW
The setting limits the heating support output.
15 kW
1 kW
N
E
Heating sup-
port hysteresis
2 – 15
Only if [Heating support (HZU)] parameter = On.
Heating support is activated if
Tdhw > T 4 K and Tdhw > [Feed temperature, target] + 1 K.
Heating support is deactivated if
Tdhw < THZUmin or Tdhw < [Feed temperature, target].
THZUmin = currently active hot water target temperature [Feed temperat-
ure, target] + set [Heating support hysteresis] parameter value.
Tdhw = current hot water storage tank temperature
[Feed temperature, target] = currently active feed target temperature (see
)
5
1
N
E
Heating sup-
port max.
temp.
5 – 85 °C
The setting limits the target feed temperature (measured against t
V, BH
)
when the heating support function is active.
60 °C
1 °C
N
E
Min. pump
power
40 – 80%
Lower limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source. During normal operation,
the pump is controlled according to the [Pump limit] parameter, see
.
50%
1%
N
E
Max. pump
power
60 – 80%
Upper limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source. During normal operation,
the pump is controlled according to the [Pump limit] parameter, see
.
80%
1%
N
E
Tab. 7-12
Parameter in the "Intelligent Storage Mgmt" menu
7.6
Configuration
[→ Main menu → Configuration]
7.6.1
Menu: Sensors
[→ Main menu → Configuration → Sensors]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Outside tem-
perature
sensor (*)
Integrated
sensor
Selection of whether the sensor integrated in the outdoor unit or an op-
tional outside temperature sensor is used to determine the target feed tem-
peratures
-
N
E
Optional sensor
Hot water
sensor
Configuration of the domestic hot water preparation:
-
N
E
Inactive
No function for domestic hot water preparation.
Sensor
Function for domestic hot water preparation is activated. A storage temper-
ature sensor is evaluated for domestic hot water preparation (if no storage
temperature sensor is connected, an error message is generated).
Thermostat
Function for domestic hot water preparation is activated. A thermostatic
switch (ON/OFF) is evaluated for domestic hot water preparation where an
"open terminal" is evaluated as "not required".
Water pres-
sure sensor
Configuration of the sensor for detecting the water pressure of the system.
-
N
E
Off
No sensor evaluation
On
Sensor evaluation activated (if no pressure sensor is connected, an error
message is generated.)
Outside tem-
perature cor-
rection
-5.0 – +5.0 K
Individual adjustment for the measured value of the outside temperature
relevant for the controller.
0.0 K
0.1 K
N
E
Water pres-
sure, min.
0.1 – 5.0 bar
Defines the minimum water pressure.
Pressure monitor function (only with activated pressure sensor, [Water
pressure sensor]= On): If the measured value falls below the set value, the
Daikin Altherma ETS(X/H) is switched off and an error message gener-
ated.
0.5 bar
0.1 bar
N
E
Содержание RoCon+ HP Series
Страница 57: ...Operating Instructions 57 Daikin RoCon HP Daikin controller RoCon HP1 008 1447899_00 09 2019 EN ...
Страница 114: ...12 Notizen Betriebsanleitung 114 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE 12 Notizen ...
Страница 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Страница 174: ...12 Notes Manuel d utilisation 174 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR 12 Notes ...
Страница 176: ...Manuel d utilisation 176 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR ...
Страница 178: ...Inhoud Gebruiksaanwijzing 178 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL Trefwoordenlijst 235 ...
Страница 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Страница 295: ...12 Appunti Istruzioni per l uso 295 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT 12 Appunti ...
Страница 297: ...Istruzioni per l uso 297 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT ...
Страница 349: ...12 Notitser Driftsvejledning 349 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA 12 Notitser ...
Страница 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Страница 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Страница 458: ...12 Notater Brukerveiledning 458 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO 12 Notater ...
Страница 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Страница 462: ...Sisällysluettelo Käyttöohje 462 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI Hakemisto 515 ...
Страница 514: ...12 Muistiinpanoja Käyttöohje 514 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI 12 Muistiinpanoja ...
Страница 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...