7
Parameter settings
Operating Instructions
34
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Bivalence
function (*)
The bivalence function is only relevant to operation of the optional heater
booster due to a backup request (room heating mode).
-
N
E
Aux. heating al-
ways possible
Operation of the backup heater is always possible.
Aux. heating T-
biv. dependent
Backup heater is only released if the temperature set in the [Bivalence
temperature] parameter is undercut.
Bivalence tem-
perature
-15 °C – +35 °C Setting influences the effect of the potential-free AUX switching contact
(toggle switch output A) defined in the [AUX switching function] parameter.
Only if [Bivalence function] parameter = heating up T-bivalence:
Outside temperature as of which the optional heater booster is activated to
support room heating. The bivalence temperature is relevant to operation
of the optional heater booster due to a backup request (room heating
mode). The temperature of the temperature sensor (information value
Temperature
A
) integrated in the heat pump outdoor unit is used for this.
0 °C
1 °C
N
E
Tab. 7-10
Parameter in the "External heat source" menu
7.5.4
Menu: Inputs/Outputs
[→ Main menu → Settings → Inputs/Outputs]
Parameters
Setting range
Min / Max
Description
Factory
setting
Incre-
ment
Access
BE
HF
Smart grid
Evaluation of the SG signal (see
-
N
E
Off
Smart Grid function not active, SG signal is not evaluated.
On
Depending on the utility company signal, the heat pump is shut off (no frost
protection function) or operated at higher temperatures.
Smart grid
mode
Only if [Smart grid] parameter = On:
Is used for a possible target temperature increase with a Smart Grid
switch-on command.
-
N
E
Comfort
Increase of the hot water target temperature by 5 K
Standard
Increase of the feed target temperature by 2 K and increase of the hot wa-
ter target temperature by 5 K
Eco
Increase of the feed target temperature by 5 K and increase of the hot wa-
ter target temperature by 7 K
HT/NT func-
tion
Setting of which heat sources are switched off if the high rate signal output
by the utility company (EVU) is received in the case of a low rate mains
connection.
-
N
E
Inactive
Deactivated (no effect)
Switch off com-
pressor
Refrigerant compressor is switched off
Switch off com-
p BUH
Refrigerant compressor and backup heater are switched off
Switch all off
Everything is switched off (no frost protection function, see
)
HT/NT contact
Definition of whether the HT/NT input is evaluated as a normally closed
contact or a normally open contact.
-
N
E
Normally open
contact
Switching contact closed during high rate.
Normally closed
contact
Switching contact closed during low rate.
Содержание RoCon+ HP Series
Страница 57: ...Operating Instructions 57 Daikin RoCon HP Daikin controller RoCon HP1 008 1447899_00 09 2019 EN ...
Страница 114: ...12 Notizen Betriebsanleitung 114 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE 12 Notizen ...
Страница 116: ...Betriebsanleitung 116 Daikin RoCon HP Daikin Regelung RoCon HP1 008 1447899_00 09 2019 DE ...
Страница 174: ...12 Notes Manuel d utilisation 174 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR 12 Notes ...
Страница 176: ...Manuel d utilisation 176 Daikin RoCon HP Régulation Daikin RoCon HP1 008 1447899_00 09 2019 FR ...
Страница 178: ...Inhoud Gebruiksaanwijzing 178 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL Trefwoordenlijst 235 ...
Страница 236: ...Gebruiksaanwijzing 236 Daikin RoCon HP Daikin regeling RoCon HP1 008 1447899_00 09 2019 NL ...
Страница 295: ...12 Appunti Istruzioni per l uso 295 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT 12 Appunti ...
Страница 297: ...Istruzioni per l uso 297 Daikin RoCon HP Regolazione Daikin RoCon HP1 008 1447899_00 09 2019 IT ...
Страница 349: ...12 Notitser Driftsvejledning 349 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA 12 Notitser ...
Страница 351: ...Driftsvejledning 351 Daikin RoCon HP Daikin regulering RoCon HP1 008 1447899_00 09 2019 DA ...
Страница 406: ...Instruktionsbok 406 Daikin RoCon HP Daikin reglerenhet RoCon HP1 008 1447899_00 09 2019 SV ...
Страница 458: ...12 Notater Brukerveiledning 458 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO 12 Notater ...
Страница 460: ...Brukerveiledning 460 Daikin RoCon HP Daikin Regulering RoCon HP1 008 1447899_00 09 2019 NO ...
Страница 462: ...Sisällysluettelo Käyttöohje 462 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI Hakemisto 515 ...
Страница 514: ...12 Muistiinpanoja Käyttöohje 514 Daikin RoCon HP Daikin ohjaus RoCon HP1 008 1447899_00 09 2019 FI 12 Muistiinpanoja ...
Страница 516: ...008 1447899_00 09 2019 EN DE FR NL IT DA SV NO FI Copyright Daikin ...