3
|
Components
Service manual
135
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
To check the fuse of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
132].
1
Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
c
a
b
a
Fuse F1U
b
Fuse F2U
c
Fuse F3U
Blown fuse on the main PCB?
Action
Yes
Replace the main PCB, see
138].
No
Return to
132] of the main PCB
and continue with the next procedure.
To check the rectifier voltage of the main PCB
Prerequisite:
First perform all earlier main PCB checks, see
132].
1
Turn ON the power of the unit.
2
Measure the voltage on the rectifier voltage check terminals (+ and –) on the
main PCB.
Result:
The measured voltage MUST be approximately 300~350 V DC.
a
b
a
+ terminal
b
– terminal