3
|
Components
Service manual
83
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
6
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
7
Heat the ends of the expansion valve pipes using an oxygen acetylene torch
and remove the expansion valve pipe ends.
8
Stop the nitrogen supply when the piping has cooled down.
9
To install the expansion valve body, see
79].
To install the expansion valve body
1
Install the expansion valve body in the correct location and correctly oriented.
2
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
3
Wrap a wet rag around the expansion valve body and solder the expansion
valve pipes to the refrigerant pipes.
CAUTION
Overheating the valve will damage or destroy it.
4
After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
a
b
c
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
a
Expansion valve pipe
b
Expansion valve body