3
|
Components
Service manual
65
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a
Compressor wire terminals cover
a
a
Compressor wire terminals cover
11
Add refrigerant to the refrigerant circuit, see
12
Install the compressor insulation, see
55].
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
3.3 Compressor thermal protector
3.3.1 Checking procedures
To perform a mechanical check of the compressor thermal protector
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
Prerequisite:
Remove the compressor insulation.
1
Remove the cover of the compressor wire terminals.
Содержание Perfera RXM R Series