Unit Configuration Setup
www .DaikinApplied .com 37
OM 1263 • MICROTECH UNIT CONTROLLER
Configuration Code Position
Description
Values (Default in Bold)
“ROC
Applicability”
16
Return Fan Type
0=None
●
6=EBMVAV
7=EBMCAV
17
Return/Exhaust Fan Capacity Control
Method
0=None
●
1=Tracking
NA
2=Building Pressure
NA
3=Speed/Network
NA
4=OADamper
NA
18
Second Duct Pressure Sensor
0=No
NA
1=Yes
19
Entering Fan Temp Sensor
0=No
NA
1=Yes
20
Energy Recovery
0=None
●
1=ConstSpdWh/NoRH
●
2=VarSpdWhl/Danfoss
●
3=VarSpdWhl/MD2
NA
4=VarSpdWhl/MD3
NA
5=VarSpdWhl/ABB
●
6=ConstSpdWhl/wRH
●
21
Cooling Circuit Type
0=Individual
NA
1=2,3 or 4 Circ . Water Condenser
NA
2=2 Circ Air Condesner
●
22
Head Pressure Control
0=No
●
1=Yes
NA
23
Bypass Valve Control
0=Slave
●
1=Bypass
NA
24,25,26
Unit Size
Three Digits (Default = 050)
●
27
Refrigerant Type
0=R22
NA
1=R407C
NA
2=R410A
●
28
Reheat Type
0=None
●
2=ModHG
●
3=StdHtRht
NA
29
Unit Voltage
0=208/60Hz
●
1=230/60Hz
●
2=460/60Hz
●
3=575/60Hz
●
4=208/50Hz
●
5=230/50Hz
●
6=460/50Hz
●
7=575/50Hz
●
30
Expansion Valve Type
0=None
●
1=EVBSag
●
4=MTIIIDF
●