Service Menus
www .DaikinApplied .com 35
OM 1263 • MICROTECH UNIT CONTROLLER
Modbus Status Menu
The Modbus Status Menu provides diagnostic information
to qualified service personnel. The items listed provide the
status of the Modbus communications with the various devices
controlled by the internal Modbus network
Table 27: Modbus Status Menu
Item Display
Name
Default Setting
Range
Password Level
SF MB Status=
—
Fault/OK
2
RFEF MB Status=
—
Fault/OK
2
OF MB Status=
—
Fault/OK
2
IFB MB Status=
—
Fault/OK
2
VCmp MB
Status=
—
Fault/OK
2
MBResistance=
Yes
No/Yess
2
ECM Config=
Done
Done
2
SetAdd1
SetAdd2
SetAdd4
SetAddCtl
SF MB Status
is a status only item which indicates the status
of the Modbus communications between the main controller
and the supply fan motor .
RFEF MB Status
is a status only item which indicates the
status of the Modbus communications between the main
controller and the return/exhaust fan motor .
OF MB Status
is a status only point to indicate if the
compressor is properly communicating with the controller via
Modbus .
IFB MB Status
. . .
VCmp MB Status
is a status only point to indicate if the
compressor is properly communicating with the controller via
Modbus .
MB Resistance
is an adjustable item used turn the main
controller’s internal Modbus termination resistor .
ECM Config
is an adjustable item used to set or change the
internal Modbus address in the supply and exhaust fan motors
.
Sensor Offsets Menu
The Sensor Offsets Menu provides a means of calibrating the
various temperature sensor inputs to the unit . Each sensor
can be “biased” by as much as +/- 10 .0°F .
Table 28:
Sensor Offset Menu
Item Display
Name
Default Setting
Range
Password Level
OA Temp=
0 .0°F
0 .0 – 10 .0°F
2
DRT1=
0 .0°F
0 .0 – 10 .0°F
2
DRT3=
0 .0°F
0 .0 – 10 .0°F
2
SRT=
0 .0°F
0 .0 – 10 .0°F
2
DFT=
0 .0°F
0 .0 – 10 .0°F
2
IRT=
0 .0°F
0 .0 – 10 .0°F
2
ORT=
0 .0°F
0 .0 – 10 .0°F
2