Passwords
Various menu functions are accessible or inaccessible,
depending on the access level of the user, and the password
they enter, if any . There are four access levels, including no
password, Level 2, Level 4, and Level 6, with Level 2 having
the highest level of access . Without entering a password, the
user has access only to basic status menu items . Entering
the Level 6 password (5321) allows access to the Alarm Lists
Menu, Quick Menu, and the View/Set Unit Menus group .
Entering the Level 4 password (2526) allows similar access
as Level 6 with the addition of the Commission Unit Menu,
Manual Control, and Service Menu groups . Entering the Level
2 password (6363) allows similar access as Level 4 with the
addition of the Unit Configuration Menu.
NOTE:
Alarms can be acknowledged without entering a
password .
The main password page is displayed when the keypad/display
is first accessed, the Home Key is pressed, the Back Key is
pressed multiple times, or if the keypad/display has been idle
longer than the Password Timeout (default 10 minutes) . The
main password page provides access to enter a password,
access the Quick Menu, view the current Unit State, access the
alarm lists or view information about the unit .
Figure 5: Password Main Page
The password field initially has a value **** where each *
represents an adjustable field. These values can be changed
by entering the Edit Mode described below .
Figure 6: Password Entry Page
Entering an invalid password has the same effect as continuing
without entering a password . Once a valid password has been
entered, the controller allows further changes and access
without requiring the user to enter a password until either the
password timer expires or a different password is entered.
The default value for this password timer is 10 minutes . It is
changeable from 3 to 30 minutes via the Timer Settings menu .
AHU 01
1/5
Enter Password
Quick Menu
Unit State=________
Alarm Lists
About This AHU
Enter Password 1/1
Enter Password
****
OM 1263 • MICROTECH UNIT CONTROLLER 8
www .DaikinApplied .com
Using the Keypad/Display