OM 1263 • MICROTECH UNIT CONTROLLER 32 www .DaikinApplied .com
Service Menus
Service Menus
Save/Restore Menu
The Save/Restore menu can be used to save or restore the
user configured parameters as well as reset the controller back
to the factory default parameters .
Table 19: Save/Restore Menu
Item Display
Name
Default Setting
Range
Password Level
Save Params=
No
No
2
Yes
Rstr Params=
No
No
2
Yes
Rstr Factory=
No
No
2
Yes
SaveToCard=
No
No
2
Yes
LoadFromCard=
No
No
2
Yes
CreateTrace=
No
No
2
Yes
TraceToSD=
No
No
2
Yes
Save Params
is an adjustable item used to save the current
parameters and configuration.
Rstr Params
is an adjustable item used to restore the current
parameters and configuration.
Rstr Factory
is an adjustable item used to restore the factory
parameters and configuration.
SaveToCard
is an adjustable item used to save the current
parameters and configuration to an SD card.
LoadFromCard
is an adjustable item used to restore the
current parameters and configuration from an SD card.
NOTE:
The controller will automatically perform a reset when
the value of Load From Card is changed from No to
Yes and the enter button is pushed .
Operating Hours
The Operating Hours menu gives a summary of the hours of
operation for each of the supply fans, return/exhaust fans,
compressors, heating and economizer operation.
Table 20: Operating Hours Menu
Item Display
Name
Default Setting
Range
Password Level
Supply Fan=
—
0 – 50000H
4
Ret/Exh Fan=
—
0 – 50000H
4
Cmp Cooling=
—
0 – 50000H
4
INV Comp=
—
0 – 50000H
4
Comp 3=
—
0 – 50000H
4
Cmp Heating=
—
0 – 50000H
4
Supply Fan
is a status item which gives the number of hours
the supply fan has operated .
Return/Exhaust Fan
is a status item which gives the number
of hours the return/exhaust fans have operated .
Cmp Cooling
is a status item which indicates the number of
hours compressor cooling has operated .
INV Comp
is a status item which indicates the number of hours
the inverter compressor has operated .
Comp 3
is a status item which indicates the number of hours
the fixed speed compressor has operated.
Cmp Heating
is a status item which indicates the number of
hours compressor heating has operated .