Troubleshooting
www .DaikinApplied .com 81
OM 1263 • MICROTECH UNIT CONTROLLER
ERROR CODE: L1 – Defective Inverter PC Board
Remote
Controller
Display
L1
Method of
Malfunction
Detection
Malfunction is detected based on the current value during waveform output before starting
compressor .
Malfunction is detected based on the value from current sensor during synchronous
operation when starting the unit . .
Malfunction
Decision
Condition
Overcurrent (OCP) flows during waveform output.
Malfunction of current sensor during synchronous operation .
IPM failure .
Supposed
Causes
●
Inverter PC board (A2P)
– IPM failure
– Current sensor failure
– Drive circuit failure