Inverter Board Fault Codes
MicroTech III communicates with the fan and compressor
inverter boards via Modbus . If the inverter boards detect
an unsafe condition they issue the appropriate control
commands and an error code can be read at the MicroTech III
display as follows:
• Go to Main menu – Alarm lists – Active alarms – Alarm
details - INV/OF Flt Code Details
• The error code is shown at “INVAlarmCode” and the error
description is shown at “Code text” as shown in
Possible Inverter Compressor fault codes are listed in
below:
Table 71: Rebel Inverter Compressor Fault Codes
Fault
Code
HMI Code Text
Extended Text
E5
Compressor Lock
Compressor Locked
L1
Current Sensor Alm
Current Sensor Alarm
L1
DC Cur Sensor Alm
DC Current Sensor Alarm
L1
EEPROM Setup Problem
EEPROM Setup Problem
L1
IGBT Problem
Insulated Gate Bipolar Transistor Problem
L1
JP Setup Problem
LP Setup Problem
L1
Momntry Ovrcurrent
Momentary Over Current
L4
Fin Temp Rise
Fin Temperature Rise
L5
Momntry Ovrcur (DC)
Momentary DC Over Current
L8
Elec Therm (Cur1)
Electrical Thermal (Current 1)
L8
Elec Therm (Cur2)
Electrical Thermal (Current 2)
L8
Elec Therm (Step)
Electrical Thermal (Out of Step)
L8
Elec Therm (Surge)
Electrical Thermal (Surge)
L8
Time Lag Ovr Current
Time Lag Over Current
L9
Stall Prevent (Strt)
Startup Prevention (Startup)
P1
Pwr Sup Imbalance
Power Supply Imbalance
P4
Fin Temp Sensor Alm
Fin Temperature Sensor Alarm
PJ
Model Setup Problem
Model Setup Problem
U2
Phase Pwr Loss
Phase Power Loss
U2
PN Short Circuit Alm
PN Electrical Short Circuit Alarm
U2
Pwr Sup Insufficient
Power Supply Insufficient
Possible outdoor fan fault codes are listed in
below .
Table 72: Rebel Outdoor Fan Fault Codes
Fault
Code
HMI Code Text
Extended Text
E7
IPM Prot Active
IPM Protection Active
E7
Momntry Ovrcurrent
Momentary Over Current
E7
Motor Lock
Motor Locked
H7
Motor Alarm
Motor Alarm
L1
EEPROM Problem
EEPROM Problem
L1
EEPROM Setup Problem
EEPROM Setup Problem
L1
JP Setup Problem
JP Setup Problem
L4
Fin Temp Rise
Fin Temperature Rise
P4
Fin Temp Sensor Alm
Fin Temperature Sensor Alarm
PJ
Model Setup Problem
Model Setup Problem
U2
Pwr Sup Voltage Alm
Power Supply Voltage Alarm
Detailed description and diagnostic instructions are shown on
the following pages .
Figure 17: Inverter Board Fault Codes
Fault Code Details
ACTIVE FAULT CODES
INVAlarmCode=______
Code Text
OF1AlarmCode=_______
Code Text
OF2AlarmCode=_______
Code Text
PREVIOUS FAULT CODES
PrvINVAlmCode=_______
Code Text
MM/DD/YYYY HH:MM:SS
PrvOF1AlmCode=______
Code Text
MM/DD/YYYY HH:MM:SS
PrvOF2AlmCode=______
Code Text