ED 15062-7 • MICROTECH II CHILLER CONTROLLER 76
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Maximum RPM
Keypad Menu Path:
No Keypad Equivalent
This output data point indicates the maximum (choke) RPM. This is the speed the Turbocor compressor
calculates above which the efficiency of the compressor falls off. (I117 & I121)
Measurement
Units
Data Type
Valid Range
Default Value
Revolutions per Minute
BACnet: RPM
BACnet: Real
BACnet: 0-32678
NA
BACnet
Compressor #1
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
55
Present Value
85
Object Name
Comp1MaxRPM
Compressor #2
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
59
Present Value
85
Object Name
Comp2MaxRPM
LONWORKS
No LONWORKS equivalent.
Maximum Send Time
Keypad Menu Path:
No Keypad Equivalent
This configuration network parameter controls the maximum period of time that expires before the
following network variables are transmitted.
• nvoChillerStat
• nvoActiveSetpt
• nvoActualCapacity
• nvoLvgChWTemp
• nvoLvgCndWTemp
• nvoEntCndWTemp
• nvoEntChWTemp
Measurement
Units
Data Type
Valid Range
Default Value
Elapsed Time
seconds
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
0–6553.4 sec
0 (no automatic update)
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
SCPT_Reference
SCPT Index
nciMaxSendTime
Chiller
time_sec
107
two bytes
SCPT_maxSendTime
49