ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Active Setpoint
Keypad Menu Path
:
Menu
\Set
\Unit SPs (3)
This output network variable indicates the current value of the setpoint temperature used to control the
temperature of the Leaving Chilled Water or Leaving Hot Water. Based on the operating mode of the
chiller, this value is derived from the Cool Setpoint, Heat Setpoint, or Ice Setpoint. The default mode is
Cooling and is used unless changed by the Mode input. (A2)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS; Fixed Point
Scalar signed long
BACnet: -40°–199° F
LONWORKS: -40°–93°C
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
7
Present Value
85
Object Name
ActiveLvgWaterTarget
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoActiveSetpt
Chiller
temp_p
105
two bytes
Actual Capacity
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates the percent of capacity the chiller is currently producing. It may
be more or less than the nominal capacity of the chiller. For Centrifugal chiller models, this data point
represents the combined percent RLA of the compressors. For positive displacement chillers (those
using screw and scroll compressors) this is a percentage of total compressors running. (A10)
Measurement
Units
Data Type
Valid Range
Default Value
Percent of chiller capacity
NA
BACnet: Real
LONWORKS: Fixed-Point
Scalar signed long
0–160%
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
9
Present Value
85
Object Name
ChillerCapacity
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoActCapacity
Chiller
lev_percent
81
two bytes