ED 15062-7 • MICROTECH II CHILLER CONTROLLER 36
www.DaikinApplied.com
d
eTaIled
d
aTa
P
oInT
I
nformaTIon
Compressor Current
Keypad Menu Path:
No Keypad Equivalent
Measurement
Units
Data Type
Valid Range
Default Value
Electric Current
BACnet: Amperes
LONWORKS: Amperes
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet:
LONWORKS: -3276.8–3276.7
NA
BACnet
Compressor Select
This output network variable indicates the current compressor amperes of the compressor selected with
. (A26)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
51
Present Value
85
Object Name
Current
Compressor #2
This variable indicates the current compressor amperes of compressor 2. (A95)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
76
Present Value
85
Object Name
Comp2Current
Compressor #3
This variable indicates the current compressor amperes of compressor 3. (A109)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
95
Present Value
85
Object Name
Comp3Current
Compressor #4
This variable indicates the current compressor amperes of compressor 4. (A114)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
103
Present Value
85
Object Name
Comp4Current
Compressor #5
This variable indicates the current compressor amperes of compressor 5. (A119)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
111
Present Value
85
Object Name
Comp5Current