ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Compressor Suction Line Temperature
Keypad Menu Path:
Menu
\View
\Unit
\Refrigerant (2)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
LONWORKS: °C
BACnet: Real
LONWORKS: Fixed Point
Scalar signed long
BACnet: -40°–244°F
LONWORKS: -40°–118°C
NA
BACnet
Compressor Select
This output network variable indicates the current suction line refrigerant temperature. There is a separate output for each
compressor. See
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
15
Present Value
85
Object Name
SuctionTemp
Compressor #2
This variable indicates the current suction line refrigerant temperature for compressor 2. Not available on all chiller models. (A88)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
69
Present Value
85
Object Name
Comp2SuctTemp
LONWORKS
Variable Details
This output network variable indicates the current suction line refrigerant temperature. There is a separate output for each
compressor. See
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoSuctionTemp
Proprietary
temp_p
105
two bytes