Compressor #4
This output network variable indicates the compressor status of the compressor 42. (I111)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
107
Present Value
85
Object Name
Comp4Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #5
This output network variable indicates the compressor status of the compressor 5. (I114)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
115
Present Value
85
Object Name
Comp5Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Compressor #6
This output network variable indicates the compressor status of the compressor 6. (I115)
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
121
Present Value
85
Object Name
Comp6Status
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
LONWORKS
No LONWORKS equivalent.