ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Chiller Mode Setpoint
Keypad Menu Path:
Menu
\Set
\Unit SP (1)
The Chiller Mode data point determines the mode of operation of the chiller. LONWORKS network
variables set the default and operating chiller mode. The BACnet property is a commandable property of
a Multi-state Output object. Refer to the appropriate Operating Manual for suitable variable values. (I17)
Measurement
Units
Data Type
Valid Range
Default Value
HVAC Mode
NA
BACnet: Unsigned Integer
LONWORKS: Fixed Point
Scalar - unsigned long
See Below
See Below
BACnet
This commandable property sets the mode of operation of the chiller and provides the ability for another node on the network to
place a chiller in another mode.
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Multi-state Output
14
45
Present Value
85
Object Name
ChillerOperationMode
Property Values
1. ICE
2. COOL
3. HEAT
Default Value (Relinquish_Default):
2
LONWORKS
Input (nvi)
This input network variable sets the mode of operation of the chiller and provides the ability for another node on the network to
place a chiller in another mode.
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
SCPT Reference
SCPT Index
nviMode
Chiller
hvac_mode
108
one byte
NA
NA
hvac_mode
All enumerations are not used for this data point. Only the following enumerations are used.
Value
Identifier
Notes
1
HVAC_HEAT
Heating only
3
HVAC_COOL
Cooling only
11
HVAC_ICE
Ice-making mode