ED 15062-7 • MICROTECH II CHILLER CONTROLLER
IGV Percentage Open
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates current percent of vanes open for each compressor (0%=closed,
110%=full capacity-open) (I120 & I124)
Measurement
Units
Data Type
Valid Range
Default Value
Percent
BACnet: %
BACnet: Real
BACnet: 0–110
NA
BACnet
Compressor #1
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
58
Present Value
85
Object Name
Comp1IGVPercentOpen
Compressor #2
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
62
Present Value
85
Object Name
Comp2IGVPercentOpen
LONWORKS
No LONWORKS equivalent.
Inverter Temperature
Keypad Menu Path:
No Keypad Equivalent
This output network variable the current drive temperature. There is one variable for each compressor.
(A86 & A106)
Measurement
Units
Data Type
Valid Range
Default Value
Temperature
BACnet: °F
BACnet: Real
BACnet: 32.0–212.0°F
NA
BACnet
Compressor #1
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
66
Present Value
85
Object Name
Comp1InverterTmp
Compressor #2
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
87
Present Value
85
Object Name
Comp2InverterTmp
LONWORKS
No LONWORKS equivalent.