d
eTaIled
d
aTa
P
oInT
I
nformaTIon
www.DaikinApplied.com
57
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Condenser Water Pump Status
Keypad Menu Path:
No Keypad Equivalent
This output network variable indicates whether the selected pump has been commanded ON or OFF.
See
Measurement
Units
Data Type
Valid Range
Default Value
Flow State
NA
BACnet: Enumerated
LONWORKS: Structure
See Below
NA
BACnet
Variable Details
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
37
Present Value
85
Object Name
CondPumpState
Property Values
0 = Off (Inactive)
1 = On (Active)
LONWORKS
Variable Details
LONWORKS Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCndWPump
Proprietary
Switch
95
two bytes
Structure
typedef struct {
unsigned
value;
signed
state;
} SNVT_switch;
Valid Range
Value Field unused
State Field 0
Pump Commanded Off
1
Pump Commanded On