IOM 1266-2 • MAGNITUDE
®
MODEL WME CHILLERS
8
www.DaikinApplied.com
I
nsTallaTIon
I
nsTallaTIon
Nameplates
There are several identification nameplates on the chiller:
• The unit nameplate is located on the exterior of the Unit
Control Panel. Both the Model No. and Serial No. are
located on the unit nameplate; the Serial No. is unique to
the unit. These numbers should be used to identify the
unit for service, parts, or warranty questions. This plate
also has the unit refrigerant charge and electrical ratings.
• Vessel nameplates are located on the evaporator and
condenser. They have a National Board Number (NB)
and a serial number, either of which identify the vessel
(but not the entire unit).
Receiving and Handling
The unit should be inspected immediately after receipt for
possible damage. All Daikin Applied centrifugal water chillers
are shipped FOB factory and all claims for handling and
shipping damage are the responsibility of the consignee.
On units with factory-installed insulation, the insulation
is removed from the vessel lifting hole (also used for
transportation tie-downs) locations and is shipped loose. It
should be secured in place after the unit is finally placed.
Neoprene vibration isolation pads are shipped loose in the
power panel. If the unit is equipped with a shipping skid, leave
the skid in place until the unit is in its final position. This will aid
in handling the equipment.
CAUTION
Extreme care must be used when rigging the unit to prevent
damage to the control panels and refrigerant piping. See the
certified dimension drawings included in the job submittal for
the weights and center of gravity of the unit. If the drawings
are not available, consult the local Daikin Applied sales office
for assistance.
The unit can be lifted by fastening the rigging hooks to the four
corners of the unit where the rigging eyes are located, see
. A spreader bar must be used between the rigging
lines to prevent damage to the control panels, piping, and
electrical panels. The spreader bar length should be equal
to, or no more than 1-foot shorter than, the distance between
the lifting holes located at opposite ends of the chiller. The
unit will require a single spreader bar of this length capable
of supporting 1.5 times the shipping weight of the unit.
Separately, all cables and hooks by themselves must also be
capable of supporting 1.5 times the shipping weight of the unit.
NOTE:
The spreader bars in
are a representation
only and may not reflect the appearance of the actual
spreader bars needed.
If a knockdown option was ordered on the unit, reference the
for more
information.
Location
WME chillers are intended only for installation in an indoor or
weather protected area consistent with the NEMA 1 rating on
the chiller, controls, and electrical panels. Equipment room
temperature for operating and standby conditions is 40°F to
104°F (4.4°C to 40°C).
NOTE:
Excessive humidity in the mechanical room should
be avoided. A limit of 90% non-condensing humidity
should be met to minimize electrical components
exposure to water condensing in panels. Humidity
levels in the mechanical room, even if lower than
90%, can cause water to condense on/near all cool
surfaces and potentially lead to premature component
wear. If possible, the mechanical room should be
conditioned which can extend the useful lifetime for
all mechanical room equipment.
Radiant heat from boilers or piping that would
adversely raise component surface temperatures
beyond ambient limits must also be avoided.
Figure 5: WME Unit Rigging
LIFT CONTROL BOX WITH
1/2" LIFTING EYES (QYT 2)
NOT SUPPLIED
LIFT VFD WITH LIFTING EYES
(QTY 4)
LIFT FULL UNIT OR INDIVIDUAL EVAPORATOR & CONDENSER FROM TUBESHEET
ROUND LIFTING HOLES. USE SPREADER BARS TO KEEP LIFT STRAPS VERTICAL.
LIFT COMPRESSOR WITH M16
LIFTING EYES (QTY 2)
NOT SUPPLIED
WME-C VINTAGE DUAL UNIT
910222350
DAIKIN APPLIED IS NOT A LICENSED NOR
CERTIFIED RIGGING SPECIALIST.
THEREFORE IT IS THE CUSTOMERS
RESPONSIBILITY TO CONSULT A CERTIFIED
RIGGING CONTRACTOR TO RIG, LIFT, AND
MOVE COMPONENTS & SUBCOMPONENTS
PROPERLY AND SAFELY AS NEEDED.