Strategy (V) VALVE SP/VFD STAGE:
This control
strategy is tower fan control with a VFD and bypass valve
.
To set up in HMI:
A. The TOWER Setpoint setting for Cooling Tower Control
strategy should be NONE. Tower Valve/VFD should be
changed to VALVE SP/VFD STAGE.
B. Use all of the same setpoint settings as outlined in
Strategy (II) - section B for Temp or section C for Lift.
Figure 53: Strategy (V) - VALVE SP/VFD STAGE
Figure 54: Strategy (V) VALVE SP/VFD STAGE -
Percent vs. Temperature
, the default minimum and maximum
VFD speeds are 20% and 100%, respectively. These minimum
and maximum values are adjustable anywhere between 0%
and 100%. Additional fans stage on when the VFD speed
reaches the maximum value that was set. In addition,
shows that the default temperature at which the valve opens
completely is 65°F. This temperature is the Valve SP (also
called Valve Target) and is adjustable.
BAS Alternate
In control strategies (I) through (V), the chiller MicroTech
®
is directly controlling the cooling tower fan staging, variable
frequency drives, and bypass valves. As an alternative, a BAS
can control these components based on a signal from the
MicroTech
®
controller. See
Figure 55: BAS Alternate
Condenser
MicroTech
®
Controller
0-10 VDC
Signal
Bypass Line
0-10 VDC Signal
Bypass
Valve
Cooling Tower
Fan Staging
(Up to 2 fans)
Tower
Control
Panel
w/ Fan
VFD
0
20
40
60
80
100
60
65
70
75
80
85
90
Per
cen
t (
%
)
Temperature (°F)
% VFD Speed (2 Fan Stages)
% VFD Speed (1 Fan Stage)
% Valve Opening
Condenser
MicroTech
®
Controller
Bypass Line
0-10 VDC Signal
BAS
Tower
Control
Panel
w/ Fan
VFD