IOM 1266-2 • MAGNITUDE
®
MODEL WME CHILLERS
42 www.DaikinApplied.com
o
peraTIon
Figure 56: Settings View - Valves
Table 17: Valve Setpoint Settings
Description
Default
Range
PW
Comments
EXV Gain
78
20-400
T
Gain selection based on chiller size and valve type.
Figure 57: Settings View - Offsets
Table 18: Offsets Setpoint Settings
Description
Default
Range
PW
Comments
Evap EWT
0.0
-1.5 to 1.5
T
Sets the offset for the sensor listed based upon jobsite calibrations.
Evap LWT
0.0
-1.5 to 1.5
T
Cond EWT
0.0
-1.5 to 1.5
T
Cond LWT
0.0
-1.5 to 1.5
T
Liquid Line Temp
0.0
-1.5 to 1.5
T
Comp Discharge Temp
0.0
-1.5 to 1.5
T
Comp Suction Temp
0.0
-1.5 to 1.5
T
Evap Pressure
0.0
-2 to 2
T
Cond Pressure
0.0
-2 to 2
T
Liquid Line Pressure
0.0
-2 to 2
T
Comp Discharge Press
0.0
-2 to 2
T
Comp Suction Press
0.0
-2 to 2
T