IOM 1266-2 • MAGNITUDE
®
MODEL WME CHILLERS
50 www.DaikinApplied.com
o
peraTIon
Compressor Controller Inputs and Outputs
The following tables list, for each compressor controller, analog inputs and digital outputs as well as the stepper motor outputs.
Table 29: Compressor Controller, Analog Inputs
#
Description
Source
Signal
Sensor Range
1
Compressor Suction Temperature
NTC Thermistor
10k @ 25°C
-40 to 125°C
2
Compressor Discharge Temperature
NTC Thermistor
10k @ 25°C
-40 to 125°C
3
Suction Refrigerant Pressure
Sealed Gage Transducer
0.5 to 4.5 VDC nominal
0 to 100 psi
4
Discharge Refrigerant Pressure
Sealed Gage Transducer
0.5 to 4.5 VDC nominal
0 to 200 psi
5
Rotor Pump Temperature
NTC Thermistor
10k @ 25°C
-40 to 125°C
6
Inlet Guide Vane Position
Rotary Transducer
1.5 to 2.6 VDC nominal
Closed to Open
7
Motor Winding Temperature 1
NTC Thermistor
10k @ 25°C
-40 to 150°C
8
Motor Winding Temperature 2
NTC Thermistor
10k @ 25°C
-40 to 150°C
9
Motor Winding Temperature 3
NTC Thermistor
10k @ 25°C
-40 to 150°C
10
Motor Case Temperature
NTC Thermistor
10k @ 25°C
-40 to 125°C
11
Motor Gap Temperature
NTC Thermistor
10k @ 25°C
-40 to 125°C
Table 30: Compressor Controller, Digital Outputs
#
Description
Load
Output OFF
Output ON
1
VFD Enable
VFD
Compressor OFF
Compressor ON
2
Liquid Injection
Solenoid (24 VDC, 20 VA max)
No Injection
Injection
3
Stator Cooling
Solenoid (24 VDC, 20 VA max)
Cooling OFF
Cooling ON
Table 31: Compressor Controller, Analog Outputs
Description
Output Signal
Sensor Range
Inlet Guide Vane Driver Position
0 to 10 VDC
0 to 100%
Rotor Cooling Driver Signal
0 to 10 VDC
0 to 100%
PLBV Driver Position
0 to 10 VDC
0 to 100%