Outline of Control (Outdoor Unit)
SiE 00-07
62
Function R-407C PLUS Series
[In heating operation]
[Defrosting in oil return mode]
SVTs turns ON continuously
SVTs is OFF at any case when STD compressor stops.
3.13.2 Operating Frequency Control
Normal operation
SVTs1 (Y4S), SVTs2 (Y6S) : ON
2 min
•
Tds1, Tds2
≥
100˚C
•
LP<0.05MPa
•
(HP+0.10) / (LP+0.10)>8
•
Tds1, Tds2<90˚C
•
LP<0.07MPa
(V0830)
OR
&
Compressor upper-limit frequency
(Nearest lower step listed below)
•
71Hz+ON+OFF
•
75Hz+OFF+OFF
•
41Hz+OFF+OFF
41Hz+OFF+OFF
Normal operation
HTdi
≥
110˚C
HTdi
≥
115˚C
HTdi>130˚C
HTdi<105˚C
Compressor stop (for 5 min)
Forced
thermostat OFF
F3 Malfunction
stop
Normal operation
HTds1, HTds2
≥
110˚C
HTds1, HTds2<105˚C
HTds1, HTds2>130˚C
∗
Malfunction reset
HTdi<115˚C
HTs1, HTs2<115˚C
HTdi, HTds1, HTds2>130˚C
(V0831)
Up to 2 times
within 100 min
HTdi : Adjusted discharge temperature
for Inverter Compressor
[INV Compressor]
[STD Compressor]
Содержание FXYBP20K7V1