SiE 00-07
Outline of Control (Outdoor Unit)
Function R-407C PLUS Series
45
3.3
Defrost Control
Activates the defrosting operation to melt frost accumulated on the outdoor heat exchanger during heating
operation.
[Defrost start conditions]
When the following conditions are met during heating operation, the defrosting operation is activated.
Tb : Distributor pipe temperature (˚C) at heat exchanger outlet (in cooling operation)
Ta : Outside temperature (˚C)
When the above conditions are met, the following “defrosting operation preparation” operation is conducted
for 2 minutes, then the defrosting operation is activated.
1. Outputs “oil return, defrost preparation” signal to indoor units.
2. Turns on the liquid injection solenoid valve (Y3S, Y4S, Y6S) based on Td or DSH.
Td : Discharge pipe temperature
DSH : Discharge super heat temp.
∗
Liquid injection : Refer to page 61 and 62.
OR
&
When cumulative compressor operating time from power On or completion of previous
defrosting operation exceeds 20 minutes
When condition (Tb
≤
B
×
Ta – A) remains for 5 minutes (–25
≤
Tb
≤
–10)
(Value of A based on the following table. When Ta
≥
7, Ta = 7˚C is used in calculation)
When forced defrost setting (local setting) is turned on and Tb < 12.5˚C
Defrost setting
Defrost change setting
B
L
M
H
Field set (mode 2)
M=factory set
A=12
A=14
A=16
Outside air Ta > 0˚C
0.6
Outside air Ta
≤
0˚C
0.8
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...