Operation Flowcharts
SiE 00-07
112
Troubleshooting R-407C PLUS Series
Preset temperature
Intake air temperature
a = b = 1 (a = b = 0.5 possible for FXYCP, FXYFP, FXYHP, FXYKP only.)
Cooling operation
Auxiliary electric heater (K1R): OFF
Humidifier (Hu) : OFF
Auxiliary electric heater (K1R): OFF
Program dry display: Cancelled
Normal operation
Set direction of air flow
Swing flap?
Recycling guard timer
ON (5 minutes)
Program dry on/off?
Program dry in operation
Moisture prevention
condition?
Moisture prevention position
Cassette: P1
Suspended :P0
YES
YES
NO
OFF
NO
Yes
ON
YES
YES
∗
4
∗
5
∗
6
(Option)
(Option)
NO
Fan M1F operating at set
volume of air flow
Drain-up kit M1P : OFF after 5
minutes residual operation
Frost
prevention operation
in progress?
Test run in progress?
Thermostat status?
(Option)
Drain-up kit M1P : ON
OFF
(Option)
Drain-up kit M1P : OFF after 5
minutes residual operation
Electronic expansion valve
Y1E : OFF
Thermostat on operation signal to
outdoor unit: Cancelled
Electronic expansion valve Y1E:
Capacity control
Thermostat ON operation signal
to outdoor unit: Output
Drain-up kit M1P : ON
A
(VF022)
NO
NO
∗
4 If the evaporator inlet temperature is -5˚C or lower for a total of 10 minutes, or is -1˚C or lower for a
total of 40 minutes, frost prevention operation is initiated. Normal operation resumes when the
temperature is +7˚C or higher for 10 consecutive minutes.
∗
5 Thermostat status
∗
6 The drain-up kit is standard equipment for models FXYCP, FXYFP, FXYKP and FXYSP.
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...