SiE 00-07
Outline of Control (Outdoor Unit)
Function R-407C PLUS Series
55
3.10
Oil Return Operation
Activates the oil return operation to collect refrigerant oil from the field pipes when the following conditions
are met.
[Start conditions]
1. When cumulative compressor operating time from power ON exceeds 2 hours
2. When cumulative compressor operating time from completion of previous return operation exceeds 8
hours.
However, when the upper-limit frequency is limited to less than “A” Hz during the previous oil return
operation, the above time period of 8 hours is changed to 4 hours.
∗
1) When defrost control operation for more than 4 minutes with inverter compressor frequency of “A”Hz or
higher, oil return time reset to 8 hours.
2) When condition 1. or 2. is satisfied during heating operation, the electric heaters of indoor units are
turned off 2 minutes prior in order to prepare for the oil return operation.
3) The oil return operation is not activated for 28 minutes after the completion of the previous defrosting
operation.
[Oil return operation]
The compressor operating frequency is set to “B” Hz shown in the following table.
[Ending conditions]
The oil return operation ends after 1~8 minutes of operation. However, when the compressor stop
conditions are met during an oil return operation, the compressor stops after the completion of the oil
return operation.
When the compressor stops during an oil return preparation operation, the oil return operation is
activated at the next startup.
When the defrost control needs more than 4 minutes above “A” condition, the timer of oil return is reset
to 8 hours
A
B
INV
STD1
STD2
INV
STD1
STD2
RSXYP16KJ
33Hz
ON
—
52Hz
ON
—
RSXYP18KJ
41Hz
ON
—
71Hz
ON
—
RSXYP20KJ
41Hz
ON
—
71Hz
ON
—
RSXYP24KJ
75Hz
ON
OFF
52Hz
ON
ON
RSXYP26·28·30KJ
75Hz
ON
OFF
52Hz
ON
ON
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...