Product Outline
SiE 00-07
4
General Information R-407C PLUS Series
Feature (3)
Reduction of installation area
Simpler piping work at installation sites
Other versatile
functions are
provided
Individual control of up to 20 indoor units with one 20HP class outdoor unit
For VRV PLUS
Others
High efficiency with power factor of 90% or higher
Cooling operation with outdoor air temperature as low as –5˚C
Heating operation with outdoor air temperature as low as –15˚C
Simple REFNET piping system
Super wiring system
Automatic address setting function
Built-in wiring error check function
Equipped with sequential start function
Nighttime low-noise mode for reduced operating sound (Option pcb DTA104A61/62 is required)
20HP
30HP
Pipe connecting locations
14 joints
→
6 joints
20 joints
→
6 joints
20HP
30HP
Conventional
system
Function-unit-less
system
11.6%reduction
13.7%reduction
(V0803)
Long refrigerant piping : equivalent
length of 125, actual length of 100 m
and height difference of 50 m.
Connection of indoor unit of varying
capacities and types totaling 130%
(max.) of outdoor unit by capacity.
From first branch to any indoor unit =
40 m.
Outdoor unit name
No. of indoor units connectable
RSXYP16~20K
20 units
RSXYP24~30K
32 units
Height difference
between indoor units
15m
100m
Actual height difference
between indoor unit and
outdoor unit
50 m
40 m
from first Branch
to last indoor unit.
(In case of the outdoor
unit located upper position
than the indoor unit)
(V0804)
(V0805)
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...