Test Operation
SiE 00-07
100
Test Operation R-407C PLUS Series
1.12.2 Wired Remote Controller – Heat Reclaim Ventilation <BRC301B61>
Setting procedure
1. In the Normal Mode, press the
button for more than 4 seconds to enter the Local Setting mode.
2. Using the
(Mode No. UP) and [Ventilation Volume] (Mode No. DOWN) buttons to select a
desired Mode No.
3. To set individual Heat Recraim Ventilation units in group control (select Mode Nos. 27 and 28 (Heat
Recraim Ventilation )), press the
button and choose the Unit No. to set. (This step is not
necessary in all group unit setting.)
4. Press the
UP button to select a Setting Switch No.
5. Press the
DOWN button to select a Setting Position No.
6. Press the
button once to enter the settings.
7. Depress the
button for about 1 second to return to the Normal Mode.
(Example)
When setting the filter sign time to "Filter Dirtiness - High" in all group unit setting, set the Mode No. to "17,"
Mode Setting No. to "0" and Setting Position No. to "02."
4
3
6
1, 7
5
2
Unit No.
Mode No.
Setting position No.
Field setting mode
Setting switch No.
(HL039)
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...