FTXM-V Series EDUS042101
3P628775-3
2
• Take into account strong winds, typhoons, or earthquakes
when installing. Improper installation may result in the unit
falling and causing accidents.
• Make sure that a separate power supply circuit is provided
for this unit and that all electrical work is carried out by
qualified personnel licensed or certified in their jurisdiction
according to local, state, and national regulations. An
insufficient power supply capacity or improper electrical
construction may lead to electric shock or fire.
•
Make sure that all wiring is secured, that specified wires are
used, and that no external forces act on the terminal connections
or wires. Improper connections or installation may result in fire.
• When wiring, position the wires so that the electrical
wiring box cover can be securely fastened. Improper
positioning of the electrical wiring box cover may result in
electric shock, fire, or the terminals overheating.
• Before touching electrical parts, turn off the unit.
• The circuit must be protected with safety devices in
accordance with local and national codes, i.e. a circuit breaker.
•
Securely fasten the outdoor unit terminal cover (panel). If the
terminal cover/panel is not installed properly, dust or water
may enter the outdoor unit causing fire or electric shock.
• When installing or relocating the system, keep the refrigerant
circuit free from substances other than the specified
refrigerant (R32) such as air. Any presence of air or other
foreign substance in the refrigerant circuit can cause an
abnormal pressure rise or rupture, resulting in injury.
• Do not change the setting of the protection devices. If the
pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those
specified by Daikin are used, fire or explosion may occur.
• When installing or relocating the air conditioner, do not let
any other substances besides R32, such as air, enter the
refrigerant circuit.
The presence of air or foreign matter in the refrigerant
circuit causes an abnormal pressure rise, which may
result in equipment damage and even injury.
• Do not use means to accelerate the defrosting process (if
possible) or to clean, other than those recommended by
the manufacturer.
• The appliance must be stored in a room without continuously
operating ignition sources (for example: open flames, an
operating gas appliance or an operating electric heater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odor.
•
Comply with national gas regulations.
CAUTION
•
Do not touch the switch with wet fingers. Touching a switch
with wet fingers can cause electric shock.
• Do not allow children to play on or around the unit to prevent injury.
• Wear adequate personal protective equipment (protective
gloves, safety glasses,…) when installing, maintaining or
servicing the system.
•
The heat exchanger fins are sharp enough to cut. To avoid
injury, wear gloves or cover the fins while working around
them.
• Do not touch the refrigerant pipes during and immediately
after operation as the refrigerant pipes may be hot or
cold, depending on the condition of the refrigerant flowing
through the refrigerant piping, compressor, and other
refrigerant cycle parts. Your hands may suffer burns or
frostbite if you touch the refrigerant pipes. To avoid injury,
give the pipes time to return to normal temperature or, if
you must touch them, be sure to wear proper gloves.
• Install drain piping to ensure proper drainage. Improper drain
piping may result in water leakage and property damage.
• Insulate piping to prevent condensation.
• Be careful when transporting the product.
• Do not turn off the power immediately after stopping
operation. Always wait for at least 5 minutes before turning
off the power. Otherwise, water leakage may occur.
• Do not use a charging cylinder. Using a charging cylinder
may cause the refrigerant to deteriorate.
• Refrigerant R32 in the system must be kept clean, dry, and tight.
(a) Clean and Dry -- Foreign materials (including mineral
oils such as SUNISO oil or moisture) should be
prevented from getting into the system.
(b)
Tight -- R32 does not contain any chlorine, does not
destroy the ozone layer, and does not reduce the earth’s
protection again harmful ultraviolet radiation. R32 can
contribute to the greenhouse effect if it is released.
Therefore take proper measures to check for the tightness
of the refrigerant piping installation. Read the chapter
Refrigerant Piping and follow the procedures.
• The outdoor unit is for R32. See the catalog for indoor
models that can be connected. Normal operation is not
possible when connected to non-compatible indoor units.
•
Remote controller (wireless kit) transmitting distance can be
shorter than expected in rooms with electronic fluorescent
lamps (inverter or rapid start types). Install the indoor unit
far away from fluorescent lamps as much as possible.
• Do not install the air conditioner or heat pump in the
following locations:
(a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen.
Plastic parts may deteriorate and fall off or result in
water leakage.
(b)
Where corrosive gas, such as sulfurous acid gas, is produced.
Corroding copper pipes or soldered parts may result in
refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of
the control system and cause the unit to malfunction.
(d) Where flammable gas may leak, where there is carbon
fiber, or ignitable dust suspension in the air, or where
volatile flammables such as thinner or gasoline are handled.
Operating the unit in such conditions can cause a fire.
• Take adequate measures to prevent the outdoor unit
from being used as a shelter by small animals. Small
animals making contact with electrical parts can cause
malfunctions, smoke, or fire. Instruct the user to keep the
area around the unit clean.
• Servicing shall be performed only as recommended by the
manufacturer and licensed or certified in their jurisdiction.
NOTE
• The outdoor unit should be positioned where the unit and power
supply wires (breaker panel to outdoor unit) are at least 10ft (3m)
away from any televisions or radios. (The unit may cause interference
with the picture or sound.) Depending on the radio waves, a distance
of 10ft (3m) may not be sufficient to eliminate the noise.
• Dismantling the unit, treatment of the refrigerant, oil and
additional parts must be done in accordance with the
relevant local, state, and national regulations.
•
Only use tools for R32 or R410A, such as a gauge
manifold, charge hose, gas leak detector, reverse flow
check valve, refrigerant charge base, vacuum gauge, or
refrigerant recovery equipment.
• If the conventional refrigerant and refrigerator oil are
mixed in R32, the refrigerant may deteriorate.
•
As maximum allowable pressure is 604psi (4.17MPa), the wall
thickness of field-installed pipes should be selected in accordance
with the relevant local, state, and national regulations.
RN004(R32)-U
01_EN_3P628775-3.indd 2
2021/02/09 13:40:04
Содержание FTXM09VVJU
Страница 1: ...Heat Pump Split Type Air Conditioners FTXM V Series EDUS042101...
Страница 2: ......
Страница 9: ...FTXM V Series EDUS042101 7 C 3D129693 FTXM18VVJU C 3D129692 FTXM09 12VVJU 4 1 Indoor Unit 4 Dimensions...
Страница 10: ...8 FTXM V Series EDUS042101 C 3D129694 FTXM24VVJU...
Страница 11: ...FTXM V Series EDUS042101 9 3D123362 RXM18VVJU 3D131944B RXM09 12VVJU 4 2 Outdoor Unit...
Страница 12: ...10 FTXM V Series EDUS042101 3D107983A RXM24VVJU...
Страница 14: ...12 FTXM V Series EDUS042101 C 3D129644B RXM18 24VVJU C 3D129643B RXM09 12VVJU 5 2 Outdoor Unit...
Страница 16: ...14 FTXM V Series EDUS042101 3D132216 RXM18VVJU 3D131979 RXM09 12VVJU 6 2 Outdoor Unit...
Страница 17: ...FTXM V Series EDUS042101 15 3D132217 RXM24VVJU...
Страница 28: ...26 FTXM V Series EDUS042101 3D133582A 8 Operation Limit...
Страница 30: ...28 FTXM V Series EDUS042101 C 3D133575 FTXM12VVJU C 3D133574 FTXM09VVJU 9 2 Indoor Unit...
Страница 31: ...FTXM V Series EDUS042101 29 C 3D133577 FTXM24VVJU C 3D133576 FTXM18VVJU...
Страница 32: ...30 FTXM V Series EDUS042101 C 3D133581 RXM12VVJU C 3D133580 RXM09VVJU 9 3 Outdoor Unit...
Страница 33: ...FTXM V Series EDUS042101 31 C 3D133618 RXM24VVJU C 3D133617 RXM18VVJU...
Страница 117: ...FTXM V Series EDUS042101 115 C 3P628774 1 Quick Reference...
Страница 148: ...146 FTXM V Series EDUS042101 1P124687 1A 13 6 DCS302C71 Central Remote Controller Installation Manual...
Страница 149: ...FTXM V Series EDUS042101 147 1P124687 1A...
Страница 150: ...148 FTXM V Series EDUS042101 1P124687 1A...
Страница 151: ...FTXM V Series EDUS042101 149 1P124687 1A...
Страница 152: ...150 FTXM V Series EDUS042101 1P124687 1A...
Страница 156: ...154 FTXM V Series EDUS042101 3P124623 1E 4 Fig 6 Fig 5 Fig 8 Fig 7...
Страница 167: ...FTXM V Series EDUS042101 165 3P124623 1E 15...
Страница 177: ...FTXM V Series EDUS042101 175 3P124623 1E 25 Fig 9 Fig 12 Fig 10 Fig 11...
Страница 178: ...176 FTXM V Series EDUS042101 3P124623 1E 26 Fig 14 Fig 13 Fig 16 Fig 15...
Страница 179: ...FTXM V Series EDUS042101 177 1P126474 1B 13 8 DCS301C71 Unified ON OFF Controller Installation Manual...
Страница 180: ...178 FTXM V Series EDUS042101 1P126474 1B...
Страница 181: ...FTXM V Series EDUS042101 179 1P126474 1B...
Страница 182: ...180 FTXM V Series EDUS042101 1P126474 1B...
Страница 183: ...FTXM V Series EDUS042101 181 1P126474 1B...
Страница 187: ...FTXM V Series EDUS042101 185 3P162015 1A 13 11 DST301BA61 Schedule Timer Controller Installation Manual...
Страница 188: ...186 FTXM V Series EDUS042101 3P162015 1A...
Страница 189: ...FTXM V Series EDUS042101 187 3P162015 1A...
Страница 190: ...188 FTXM V Series EDUS042101 3P162015 1A...
Страница 191: ...FTXM V Series EDUS042101 189 3P162015 1A...
Страница 207: ...FTXM V Series EDUS042101 205 3P534932 1D 13 14 KPW063B4 Air Direction Adjustment Grille...
Страница 208: ...206 FTXM V Series EDUS042101 3P534932 1D...
Страница 209: ...FTXM V Series EDUS042101 207 2P403095 1 13 15 KKG063A42 Back Protection Wire Net...
Страница 229: ...FTXM V Series EDUS042101 227 3P436071 1 13 21 KPS063A41 Snow Hood Intake Side Plate...
Страница 230: ...228 FTXM V Series EDUS042101 3P436071 1...
Страница 231: ...FTXM V Series EDUS042101 229 3P436072 1 13 22 KPS063A44 Snow Hood Intake Rear Plate...
Страница 232: ...230 FTXM V Series EDUS042101 3P436072 1...
Страница 233: ...FTXM V Series EDUS042101 231 3P436073 1 13 23 KPS063A47 Snow Hood Outlet...
Страница 234: ...232 FTXM V Series EDUS042101 3P436073 1...
Страница 235: ......