![Daikin FTXM09VVJU Скачать руководство пользователя страница 122](http://html1.mh-extra.com/html/daikin/ftxm09vvju/ftxm09vvju_engineering-data_2459461122.webp)
120
FTXM-V Series EDUS042101
3P627027-1
Installation space requirements
WARNING
If appliances contain R32 refrigerant, the floor area of
the room in which the appliances are installed, operated
and stored MUST be larger than the minimum floor
area A (ft
2
) defined in the table. (Refer to “Minimum
required floor area for each refrigerant amount charged”
on page 1.) This applies to:
• Indoor units
without
a refrigerant leakage sensor; in
case of indoor units
with
refrigerant leakage sensor,
consult the installation manual
•
Outdoor units installed or stored indoors (e.g. yard,
garage, machinery room)
• Pipework in unventilated spaces
NOTICE
•
Pipework should be protected from physical damage.
•
Installation of pipework should be kept to a minimum.
To determine the minimum floor area
1. Determine the total refrigerant charge in the system
(= factory refrigerant
additional refrigerant
amount charged).
2.
Determine which graph or table to use.
• For indoor units: Is the unit ceiling-mounted, wall-mounted
or floor-standing?
•
For outdoor units installed or stored indoors, and field
piping in unventilated spaces, this depends on the
installation height:
If the installation height is… Then use the graph or table
for…
<5.9ft
Floor-standing units
5.9≤×<7.2ft
Wall-mounted units
≥7.2ft
Ceiling-mounted units
3. Use the graph or table to determine the minimum floor area.
See figure 1 on the inside of the front cover.
ft
Total refrigerant charge in the system
A
min
Minimum floor area
(a)
Ceiling-mounted unit
(b)
Wall-mounted unit
(c)
Floor-standing unit
1-3-3 Refrigerant
If applicable. See the installation manual or installer reference
guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with
applicable legislation. ISO 5149 is the applicable
standard.
NOTICE
Make sure the field piping and connections are NOT
subjected to stress.
WARNING
During tests, NEVER pressurize the product with a
pressure higher than the maximum allowable pressure
(as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant
leakage. If refrigerant gas leaks, ventilate the area
immediately.
Possible risks:
• Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
•
In case of R410A or R32 refrigerant: Toxic gas might
be produced if refrigerant gas comes into contact with
fire.
• In case of CO
2
refrigerant: Refrigerant gas is toxic in
high concentrations.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage.
If you want to
pump down the system, and there is a leak in the
refrigerant circuit:
• Do NOT use the unit’s automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit.
Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
• Use a separate recovery system so that the unit’s
compressor does NOT have to operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them
directly into the environment. Use a vacuum pump to
evacuate the installation.
Ensure that the outlet for the vacuum pump is not close
to any potential ignition sources and that ventilation is
available.
WARNING: RISK OF FIRE.
•
Flammable refrigerant used. To be repaired only by
trained service personnel. Do NOT puncture
refrigerant tubing.
• Dispose of properly in accordance with federal or local
regulations. Flammable refrigerant used.
•
Flammable refrigerant used. Consult repair manual/
owner’s guide before attempting to service this
product. All safety precautions must be followed.
•
Risk of fire due to flammable refrigerant used. Follow
handling instructions carefully in compliance with
national regulations.
5
01_EN_3P627027-1.indd 5
2021/02/08 15:05:33
Содержание FTXM09VVJU
Страница 1: ...Heat Pump Split Type Air Conditioners FTXM V Series EDUS042101...
Страница 2: ......
Страница 9: ...FTXM V Series EDUS042101 7 C 3D129693 FTXM18VVJU C 3D129692 FTXM09 12VVJU 4 1 Indoor Unit 4 Dimensions...
Страница 10: ...8 FTXM V Series EDUS042101 C 3D129694 FTXM24VVJU...
Страница 11: ...FTXM V Series EDUS042101 9 3D123362 RXM18VVJU 3D131944B RXM09 12VVJU 4 2 Outdoor Unit...
Страница 12: ...10 FTXM V Series EDUS042101 3D107983A RXM24VVJU...
Страница 14: ...12 FTXM V Series EDUS042101 C 3D129644B RXM18 24VVJU C 3D129643B RXM09 12VVJU 5 2 Outdoor Unit...
Страница 16: ...14 FTXM V Series EDUS042101 3D132216 RXM18VVJU 3D131979 RXM09 12VVJU 6 2 Outdoor Unit...
Страница 17: ...FTXM V Series EDUS042101 15 3D132217 RXM24VVJU...
Страница 28: ...26 FTXM V Series EDUS042101 3D133582A 8 Operation Limit...
Страница 30: ...28 FTXM V Series EDUS042101 C 3D133575 FTXM12VVJU C 3D133574 FTXM09VVJU 9 2 Indoor Unit...
Страница 31: ...FTXM V Series EDUS042101 29 C 3D133577 FTXM24VVJU C 3D133576 FTXM18VVJU...
Страница 32: ...30 FTXM V Series EDUS042101 C 3D133581 RXM12VVJU C 3D133580 RXM09VVJU 9 3 Outdoor Unit...
Страница 33: ...FTXM V Series EDUS042101 31 C 3D133618 RXM24VVJU C 3D133617 RXM18VVJU...
Страница 117: ...FTXM V Series EDUS042101 115 C 3P628774 1 Quick Reference...
Страница 148: ...146 FTXM V Series EDUS042101 1P124687 1A 13 6 DCS302C71 Central Remote Controller Installation Manual...
Страница 149: ...FTXM V Series EDUS042101 147 1P124687 1A...
Страница 150: ...148 FTXM V Series EDUS042101 1P124687 1A...
Страница 151: ...FTXM V Series EDUS042101 149 1P124687 1A...
Страница 152: ...150 FTXM V Series EDUS042101 1P124687 1A...
Страница 156: ...154 FTXM V Series EDUS042101 3P124623 1E 4 Fig 6 Fig 5 Fig 8 Fig 7...
Страница 167: ...FTXM V Series EDUS042101 165 3P124623 1E 15...
Страница 177: ...FTXM V Series EDUS042101 175 3P124623 1E 25 Fig 9 Fig 12 Fig 10 Fig 11...
Страница 178: ...176 FTXM V Series EDUS042101 3P124623 1E 26 Fig 14 Fig 13 Fig 16 Fig 15...
Страница 179: ...FTXM V Series EDUS042101 177 1P126474 1B 13 8 DCS301C71 Unified ON OFF Controller Installation Manual...
Страница 180: ...178 FTXM V Series EDUS042101 1P126474 1B...
Страница 181: ...FTXM V Series EDUS042101 179 1P126474 1B...
Страница 182: ...180 FTXM V Series EDUS042101 1P126474 1B...
Страница 183: ...FTXM V Series EDUS042101 181 1P126474 1B...
Страница 187: ...FTXM V Series EDUS042101 185 3P162015 1A 13 11 DST301BA61 Schedule Timer Controller Installation Manual...
Страница 188: ...186 FTXM V Series EDUS042101 3P162015 1A...
Страница 189: ...FTXM V Series EDUS042101 187 3P162015 1A...
Страница 190: ...188 FTXM V Series EDUS042101 3P162015 1A...
Страница 191: ...FTXM V Series EDUS042101 189 3P162015 1A...
Страница 207: ...FTXM V Series EDUS042101 205 3P534932 1D 13 14 KPW063B4 Air Direction Adjustment Grille...
Страница 208: ...206 FTXM V Series EDUS042101 3P534932 1D...
Страница 209: ...FTXM V Series EDUS042101 207 2P403095 1 13 15 KKG063A42 Back Protection Wire Net...
Страница 229: ...FTXM V Series EDUS042101 227 3P436071 1 13 21 KPS063A41 Snow Hood Intake Side Plate...
Страница 230: ...228 FTXM V Series EDUS042101 3P436071 1...
Страница 231: ...FTXM V Series EDUS042101 229 3P436072 1 13 22 KPS063A44 Snow Hood Intake Rear Plate...
Страница 232: ...230 FTXM V Series EDUS042101 3P436072 1...
Страница 233: ...FTXM V Series EDUS042101 231 3P436073 1 13 23 KPS063A47 Snow Hood Outlet...
Страница 234: ...232 FTXM V Series EDUS042101 3P436073 1...
Страница 235: ......